Product Model
A0B 100 TMF 63-630 3p F F

Selling Points
- 1High Electrical Durability: 1500 cycles
- 2Mechanical Durability: Up to 8500 operations
- 3Thermal-Magnetic Release (TMF) for Enhanced Protection
- 4Front Terminal Connection for Easy Installation
- 5Rated for 63 A Main Circuit Current
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 9AKK108467A6707 | Product Net Width | 76.2 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 60 mm |
Product Net Weight | 0.75 kg | Product Main Type | SACE FORMULA |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Electrical Durability | 1500 cycle |
Mechanical Durability | Nr. Operations 8500 cycle | Number of Poles | 3 |
Rated Current (In) | Main Circuit 63 A | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Rated Insulation Voltage (Ui) | 690 V | Rated Operational Voltage | 415 V AC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 5 kA (380 V AC) 5 kA (415 V AC) 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 10 kA (380 V AC) 7.5 kA (415 V AC) 7.5 kA |
Rated Uninterrupted Current (Iu) | 100 A | Release | TMF |
Release Type | TM | Short-Circuit Performance Level | B |
Standards | IEC | Sub-type | A0 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA079807R1 |
Specifications may be subject to change without notice