Product Model
A1A 125 TMF 100-1000 4p F F

Selling Points
- 1High-Performance Circuit Protection: The ABB A1A 125 TMF 100-1000 4p F F offers robust short-circuit breaking capacities up to 52.5 kA.
- 2Thermomagnetic Release: Equipped with a TMF release type, providing reliable thermal and magnetic protection.
- 3Front Terminal Connection: Easy installation with front terminal connections, enhancing user convenience.
- 4Compliance with IEC Standards: Meets IEC standards for power circuit-breakers, ensuring high-quality performance.
- 5Durable Design: Designed for 1500 electrical cycles and 8500 mechanical cycles, ensuring long-lasting operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 1SDL000183R0001 9AKK108467A6707 | Product Net Width | 101.6 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 60 mm |
Product Net Weight | 1 kg | Product Main Type | SACE FORMULA |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Electrical Durability | 1500 cycle |
Mechanical Durability | Nr. Operations 8500 cycle | Number of Poles | 4P |
Opening Time | CB with SOR 15 ms CB with UVR 15 ms | Power Loss | at Rated Operating Conditions per Pole 8 W |
Rated Current (In) | Main Circuit 100 A | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Rated Insulation Voltage (Ui) | 690 V | Rated Operational Voltage | 550 V AC 250 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 12.5 kA (380 V AC) 5 kA (415 V AC) 5 kA (440 V AC) 4 kA (480 V AC) 3.75 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 2.5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 10 kA (380 V AC) 10 kA (415 V AC) 10 kA (440 V AC) 8 kA (480 V AC) 7.5 kA (500 V AC) 5 kA (250 V DC) 5 kA |
Rated Uninterrupted Current (Iu) | 125 A | Release | TMF |
Release Type | TM | Short-Circuit Performance Level | A |
Standards | IEC | Sub-type | A1 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | eClass | V11.1 : 27370409 |
Manufacturer ID | 1SDA066534R1 |
Specifications may be subject to change without notice