Product Model
A1N 125 MF 40-480 3p F F

Selling Points
- 1Robust Short-Circuit Protection: Safely handles high currents up to 40 A and withstands impulses up to 6 kV.
- 2Reliable Performance: Designed for 1500 cycles of electrical durability and 8500 cycles of mechanical durability.
- 3Advanced Features: Equipped with thermomagnetic release (TMF) for efficient operation and quick response.
- 4Compliance and Certifications: Meets EU RoHS and CE standards, ensuring environmental and safety compliance.
- 5Versatile Application: Suitable for various industrial and commercial environments, including transformer and generator protection.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Environmental Information | 1SDL000183R0001 9AKK108467A6707 | Product Net Width | 76.2 mm |
Product Net Height | 130 mm | Product Net Depth / Length | 60 mm |
Product Net Weight | 0.75 kg | Product Main Type | SACE FORMULA DSA |
Product Name | Moulded Case Circuit Breaker | Product Type | Automatic Circuit Breaker |
Version | F | Electrical Durability | 1500 cycle |
Mechanical Durability | Nr. Operations 8500 cycle | Number of Poles | 3P |
Rated Current (In) | Main Circuit 40 A | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Rated Insulation Voltage (Ui) | 690 V | Rated Operational Voltage | 550 V AC 250 V DC |
Rated Service Short-Circuit Breaking Capacity (Ics) | (240 V AC) 50 kA (380 V AC) 18 kA (415 V AC) 7.5 kA (440 V AC) 6.25 kA (480 V AC) 4.5 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 5 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (240 V AC) 100 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (480 V AC) 18 kA (500 V AC) 10 kA (250 V DC) 10 kA |
Rated Uninterrupted Current (Iu) | 125 A | Release | MF |
Release Type | M | Short-Circuit Performance Level | N |
Standards | IEC | Sub-type | A1 |
Terminal Connection Type | Front | ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
eClass | V11.1 : 27370409 | Manufacturer ID | 1SDA076710R1 |
Specifications may be subject to change without notice