Product Model

A1N 125 TMF 60-600 2p F F

In Stock
Last updated: 2025/4/21
ABB A1N 125 TMF 60-600 2p F F

Selling Points

  • 125 kA for reliable operation.
  • 2Suitable for 125 A frame size.
  • 3Meets international safety standards.
  • 4Ideal for 60-600 A applications.
  • 5Front terminals and thermomagnetic release ensure long-lasting performance.
Product Details
A1N 125 TMF 60-600 2p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
1SDL000183R0001 9AKK108467A6707
Product Net Width
50.8 mm
Product Net Height
130 mm
Product Net Depth / Length
60 mm
Product Net Weight
0.541 kg
Product Main Type
SACE FORMULA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
1500 cycle
Mechanical Durability
Nr. Operations 8500 cycle
Number of Poles
2P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Power Loss
at Rated Operating Conditions per Pole 6 W
Rated Current (In)
Main Circuit 60 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 7.5 kA (440 V AC) 6.25 kA (480 V AC) 4.5 kA (500 V AC) 2.5 kA (250 V DC) 2 Poles in Series 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 25 kA (480 V AC) 18 kA (500 V AC) 10 kA (250 V DC) 10 kA
Rated Uninterrupted Current (Iu)
125 A
Release
TMF
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
A1
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA066502R1

Specifications may be subject to change without notice