Product Model

A2C 125 MF 100-1200 3p F F

In Stock
Last updated: 2025/4/21
ABB A2C 125 MF 100-1200 3p F F

Selling Points

  • 1High-quality construction for reliable performance.
  • 2Effective protection against overloads and short circuits.
  • 3Compact design suitable for tight spaces.
  • 4Easy operation with a convenient handle mechanism.
  • 5Meets international standards for compliance and safety.
Product Details
A2C 125 MF 100-1200 3p F F
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Environmental Information
1SDL000183R0001 9AKK108467A6707
Product Net Width
105 mm
Product Net Height
150 mm
Product Net Depth / Length
60 mm
Product Net Weight
1.3 kg
Product Main Type
SACE FORMULA DSA
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Electrical Durability
4000 cycle
Mechanical Durability
10000 cycle
Number of Poles
3P
Rated Current (In)
Main Circuit 100 A
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Insulation Voltage (Ui)
690 V
Rated Operational Voltage
550 V AC 250 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(240 V AC) 25 kA (380 V AC) 12.5 kA (415 V AC) 12.5 kA (440 V AC) 10 kA (480 V AC) 9 kA (500 V AC) 4 kA (250 V DC) 2 Poles in Series 12.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(240 V AC) 50 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 20 kA (480 V AC) 18 kA (500 V AC) 8 kA (250 V DC) 2 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
125 A
Release
MF
Release Type
M
Short-Circuit Performance Level
C
Standards
IEC
Sub-type
A2
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA076720R1

Specifications may be subject to change without notice