Product Model

AF116B-30-22RT-13

In Stock
Last updated: 2025/4/18
ABB AF116B-30-22RT-13

Selling Points

  • 1Wide control voltage range (24-60 V AC, 20-60 V DC) for adaptable applications.
  • 2Built-in surge protection ensures reliable operation in unstable networks.
  • 3Compact design with ring-tongue connections for easy installation and reduced panel space.
  • 4Pre-mounted auxiliary contacts for enhanced functionality and flexibility.
  • 5Suitable for motor control up to 55 kW / 75 HP and power circuit switching up to 160 A (AC-1).
Product Details
AF116B-30-22RT-13
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
90 mm
Product Net Depth / Length
126 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Standards
IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives.
Rated Operational Voltage
Main Circuit 690 V
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 160 A (690 V) 60 °C 145 A (690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 116 A (440 V) 55 °C 116 A (500 V) 55 °C 110 A (690 V) 55 °C 65 A (380 / 400 V) 55 °C 116 A (220 / 230 / 240 V) 55 °C 116 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 116 A (440 V) 60 °C 116 A (500 V) 60 °C 110 A (690 V) 60 °C 65 A (380 / 400 V) 60 °C 116 A (220 / 230 / 240 V) 60 °C 116 A
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW (440 V) 75 kW (500 V) 75 kW (690 V) 55 kW (380 / 400 V) 55 kW (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW (440 V) 75 kW (500 V) 75 kW (690 V) 55 kW (380 / 400 V) 55 kW (220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 160 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 160 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (175 V) 2 Poles in Series, 40 °C 160 A (175 V) 2 Poles in Series, 60 °C 145 A (175 V) 2 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 160 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (260 V) 3 Poles in Series, 40 °C 160 A (260 V) 3 Poles in Series, 60 °C 145 A (260 V) 3 Poles in Series, 70 °C 130 A (72 V) 1-Pole, 40 °C 160 A (72 V) 1-Pole, 60 °C 145 A (72 V) 1-Pole, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 160 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 160 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A (90 V) 1 Pole, 40 °C 160 A (90 V) 1 Pole, 60 °C 145 A (90 V) 1 Pole, 70 °C 130 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 145 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 145 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 145 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 145 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 145 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 145 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 145 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 145 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz / 60 Hz 100 ... 250 V DC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Terminal Type
Main Circuit: Bars
General Use Rating UL/CSA
(600 V AC) 160 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 30 hp (220 ... 240 V AC) Three Phase 40 hp (440 ... 480 V AC) Three Phase 75 hp (550 ... 600 V AC) Three Phase 100 hp
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Manufacturer ID
1SFL427062R1322

Specifications may be subject to change without notice