Product Model
AF116B-40-22-11

Selling Points
- 1Wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC) for managing large control voltage variations.
- 2Built-in surge protection for a compact and reliable solution.
- 3Pre-mounted auxiliary contacts and standard ferrules for easy installation.
- 4Controls motors up to 55 kW / 400 V AC (AC-3) and switches power circuits up to 160 A (AC-1).
- 5Block type design allows easy extension with add-on auxiliary contact blocks and accessories.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 120 mm | Product Net Depth / Length | 128 mm |
Product Net Height | 150 mm | Product Net Weight | 2.05 kg |
Number of Main Contacts NO | 4 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 2 | Number of Auxiliary Contacts NC | 2 |
Rated Operational Voltage | Main Circuit 690 V | Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 160 A (690 V) 60 °C 145 A (690 V) 70 °C 130 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 116 A (440 V) 55 °C 116 A (380 / 400 V) 55 °C 116 A (220 / 230 / 240 V) 55 °C 116 A | Rated Operational Power AC-3 (Pe) | (415 V) 55 kW (440 V) 75 kW (500 V) 75 kW (690 V) 55 kW (380 / 400 V) 55 kW (220 / 230 / 240 V) 30 kW |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A | Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 160 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 160 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (175 V) 2 Poles in Series, 40 °C 160 A (175 V) 2 Poles in Series, 60 °C 145 A (175 V) 2 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 160 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (260 V) 3 Poles in Series, 40 °C 160 A (260 V) 3 Poles in Series, 60 °C 145 A (260 V) 3 Poles in Series, 70 °C 130 A (350 V) 4 Poles in Series, 40 °C 200 A (350 V) 4 Poles in Series, 60 °C 145 A (350 V) 4 Poles in Series, 70 °C 130 A (72 V) 1-Pole, 40 °C 160 A (72 V) 1-Pole, 60 °C 145 A (72 V) 1-Pole, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 160 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 160 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A (90 V) 1 Pole, 40 °C 160 A (90 V) 1 Pole, 60 °C 145 A (90 V) 1 Pole, 70 °C 130 A |
Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 145 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 145 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 145 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 145 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A | Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 145 A (110 V) 2 Poles in Series, 60 °C 145 A (110 V) 2 Poles in Series, 70 °C 130 A (110 V) 3 Poles in Series, 40 °C 145 A (110 V) 3 Poles in Series, 60 °C 145 A (110 V) 3 Poles in Series, 70 °C 130 A (220 V) 3 Poles in Series, 40 °C 145 A (220 V) 3 Poles in Series, 60 °C 145 A (220 V) 3 Poles in Series, 70 °C 130 A (72 V) 2 Poles in Series, 40 °C 145 A (72 V) 2 Poles in Series, 60 °C 145 A (72 V) 2 Poles in Series, 70 °C 130 A (72 V) 3 Poles in Series, 40 °C 145 A (72 V) 3 Poles in Series, 60 °C 145 A (72 V) 3 Poles in Series, 70 °C 130 A |
Mechanical Durability | 5 million | Maximum Mechanical Switching Frequency | 300 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz / 60 Hz 24 ... 60 V DC Operation 20 ... 60 V | Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A Pull-in at Max. Rated Control Circuit Voltage DC 210 W |
Terminal Type | Main Circuit: Bars | General Use Rating UL/CSA | (600 V AC) 160 A |
Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 15 Hp (200 V AC) Three Phase 30 hp (208 V AC) Three Phase 30 hp (220 ... 240 V AC) Three Phase 20 Hp (220 ... 240 V AC) Three Phase 40 hp (440 ... 480 V AC) Three Phase 40 Hp (440 ... 480 V AC) Three Phase 75 hp (550 ... 600 V AC) Three Phase 50 Hp (550 ... 600 V AC) Three Phase 100 hp | Object Classification Code | Q |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
UNSPSC | 39121529 | IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
E-Number (Sweden) | 3210460 | Manufacturer ID | 1SFL427263R1122 |
Specifications may be subject to change without notice