Product Model
AF265-30-11-31

Selling Points
- 1Manages large control voltage variations (24-60 V AC/DC).
- 2Built-in surge protection ensures reliable operation in unstable networks.
- 3Block type design with pre-mounted auxiliary contacts for easy extension.
- 4Controls motors up to 132 kW / 400 V AC (AC-3) or 200 hp / 480 V UL.
- 5Reduces panel energy consumption with advanced AF technology.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 140 mm | Product Net Depth / Length | 191 mm |
Product Net Height | 225 mm | Product Net Weight | 3.9 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 1 |
Rated Operational Voltage | Main Circuit 1000 V | Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 400 A | Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 350 A (1000 V) 60 °C 300 A (1000 V) 70 °C 240 A (690 V) 40 °C 400 A (690 V) 60 °C 350 A (690 V) 70 °C 290 A |
Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 265 A (440 V) 60 °C 265 A (500 V) 60 °C 250 A (690 V) 60 °C 250 A (1000 V) 60 °C 113 A (380 / 400 V) 60 °C 265 A (220 / 230 / 240 V) 60 °C 265 A | Rated Operational Power AC-3 (Pe) | (415 V) 132 kW (440 V) 160 kW (500 V) 160 kW (690 V) 200 kW (1000 V) 160 kW (380 / 400 V) 132 kW (220 / 230 / 240 V) 75 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A | Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3800 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3300 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour | Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 1000 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV | Mechanical Durability | 5 million |
Maximum Mechanical Switching Frequency | 300 cycles per hour | Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V 60 Hz 24...60 V DC Operation 20...60 V |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 9 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 3 W Holding at Max. Rated Control Circuit Voltage 60 Hz 9 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 3 W Holding at Max. Rated Control Circuit Voltage DC 3.5 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 475 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 475 V·A Pull-in at Max. Rated Control Circuit Voltage DC 400 W | Operate Time | Between Coil De-energization and NO Contact Opening 45 ... 80 ms Between Coil Energization and NO Contact Closing 30 ... 60 ms |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1x 0.75 ... 2.5 mm² Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 1x 0.75 ... 2.5 mm² Flexible 2x 0.75 ... 2.5 mm² Solid 1x 1 ... 4 mm² Solid 2x 1 ... 4 mm² Stranded 1x 1 ... 4 mm² Stranded 2x 1 ... 4 mm² | Wire Stripping Length | Auxiliary Circuit 9 mm Control Circuit 9 mm |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 | Terminal Type | Main Circuit: Bars |
NEMA Size | 5 | Continuous Current Rating NEMA | 270 A |
Horsepower Rating NEMA | (200 V AC) Three Phase 75 Hp (230 V AC) Three Phase 100 Hp (460 V AC) Three Phase 200 Hp (575 V AC) Three Phase 200 Hp | Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
General Use Rating UL/CSA | (600 V AC) 350 A | Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 75 hp (220 ... 240 V AC) Three Phase 100 hp (440 ... 480 V AC) Three Phase 200 hp (550 ... 600 V AC) Three Phase 250 hp |
Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb Control Circuit 9 in·lb Main Circuit 372 in·lb | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Object Classification Code | Q |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
UNSPSC | 39121529 | IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
Manufacturer ID | 1SFL547002R3111 |
Specifications may be subject to change without notice