Product Model
AF265-30-22-11

Selling Points
- 1High power ratings up to 250 HP.
- 2Compatible with 24 to 60 VAC and 20 to 60 VDC.
- 33NO contact configuration with 400 A at 690 V.
- 4Built-in surge suppression and short voltage dip resistance.
- 5Add-on auxiliary contact blocks for side mounting and extensive accessory options.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 140 mm | Product Net Depth / Length | 180 mm |
Product Net Height | 225 mm | Product Net Weight | 3.9 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 2 | Number of Auxiliary Contacts NC | 2 |
Rated Operational Voltage | Main Circuit 1000 V | Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 400 A | Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 350 A (1000 V) 55 °C 300 A (1000 V) 60 °C 300 A (1000 V) 70 °C 240 A (690 V) 40 °C 400 A (690 V) 55 °C 350 A (690 V) 70 °C 290 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 265 A (440 V) 55 °C 265 A (500 V) 55 °C 250 A (690 V) 55 °C 250 A (1000 V) 55 °C 113 A (380 / 400 V) 55 °C 265 A (220 / 230 / 240 V) 55 °C 265 A | Rated Operational Power AC-3 (Pe) | (415 V) 132 kW (440 V) 160 kW (500 V) 160 kW (690 V) 200 kW (1000 V) 160 kW (380 / 400 V) 132 kW (220 / 230 / 240 V) 75 kW |
Rated Breaking Capacity AC-3 | 8 x Ie AC-3 | Rated Making Capacity AC-3 | 10 x Ie AC-3 |
Short-Circuit Protective Devices | gG Type Fuses 500 A | Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3800 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 3300 A | Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A | Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A |
Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A | Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kV | Mechanical Durability | 5 million |
Maximum Mechanical Switching Frequency | 300 cycles per hour | Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ⤠70 °C) |
Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation 20 ... 60 V | Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 8.5 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 8.5 V·A Holding at Max. Rated Control Circuit Voltage DC 3 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 475 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 475 V·A Pull-in at Max. Rated Control Circuit Voltage DC 400 W |
Operate Time | Between Coil De-energization and NO Contact Opening 37 ... 47 ms Between Coil Energization and NO Contact Closing 25 ... 55 ms | Connecting Capacity Main Circuit | Flexible 2 x 70 ... 185 mm² Rigid Al-Cable 1 x 185 ... 240 mm² Rigid Cu-Cable 2 x 70 ... 185 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 1 x 1 .... 4 mm² | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Terminal Type | Main Circuit: Bars | NEMA Size | 5 |
Continuous Current Rating NEMA | 270 A | Horsepower Rating NEMA | (200 V AC) Three Phase 75 Hp (230 V AC) Three Phase 100 Hp (460 V AC) Three Phase 200 Hp (575 V AC) Three Phase 200 Hp |
Maximum Operating Voltage UL/CSA | Main Circuit 1000 V | General Use Rating UL/CSA | (600 V AC) 350 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 75 hp (208 V AC) Three Phase 75 hp (220 ... 240 V AC) Three Phase 100 hp (440 ... 480 V AC) Three Phase 200 hp (550 ... 600 V AC) Three Phase 250 hp | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Object Classification Code | Q |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
UNSPSC | 39121529 | IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
E-Number (Finland) | 3706469 | Manufacturer ID | 1SFL547002R1122 |
Specifications may be subject to change without notice