Product Model
AF2850-30-11-70

Selling Points
- 1Operates from 100-250 V AC/DC, 50/60 Hz, ensuring compatibility in various network conditions.
- 2Handles surges without affecting the control circuit, reducing the need for external surge suppressors.
- 3Up to 80% energy reduction, allowing for smaller control transformers and cabinets.
- 4Narrow width and block type design for easy integration into control panels.
- 5Switches power circuits up to 2850 A (AC-1) or 2850 A UL general use, making it suitable for heavy-duty applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 438 mm | Product Net Depth / Length | 244 mm |
Product Net Height | 422 mm | Product Net Weight | 43 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 1 |
Rated Operational Voltage | Main Circuit 1000 V | Rated Frequency (f) | Main Circuit 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 2850 A | Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 2850 A (1000 V) 55 °C 2600 A (1000 V) 70 °C 2300 A (690 V) 40 °C 2850 A (690 V) 55 °C 2600 A (690 V) 70 °C 2300 A |
Maximum Electrical Switching Frequency | (AC-1) 15 cycles per hour | Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 1000 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kV | Mechanical Durability | 0.3 million |
Maximum Mechanical Switching Frequency | 60 cycles per hour | Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at θ ⤠70 °C) |
Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V | Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 48 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 48 V·A Holding at Max. Rated Control Circuit Voltage DC 20.5 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 2450 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 2540 V·A Pull-in at Max. Rated Control Circuit Voltage DC 2290 W |
Operate Time | Between Coil De-energization and NC Contact Closing 35 ... 55 ms Between Coil De-energization and NO Contact Opening 35 ... 55 ms Between Coil Energization and NC Contact Opening 50 ... 80 ms Between Coil Energization and NO Contact Closing 50 ... 80 ms | Connecting Capacity Main Circuit | Bar 100 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm² | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Terminal Type | Main Circuit: Bars | Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
General Use Rating UL/CSA | (1000 V AC) 2850 A (600 V AC) 2850 A | Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Object Classification Code | Q |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
UNSPSC | 39121529 | IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors |
Manufacturer ID | 1SFL687001R7011 |
Specifications may be subject to change without notice