Product Model
AF38ZB-22-00RT-21

Selling Points
- 1Controls motors up to 11 kW / 400 V AC (AC-3).
- 2Switches power circuits up to 55 A (AC-1) or 55 A UL general use.
- 3Wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC).
- 4Built-in surge protection for a compact solution.
- 5Easy extension with add-on auxiliary contact blocks and various accessories.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 45 mm | Product Net Depth / Length | 101 mm |
Product Net Height | 86 mm | Product Net Weight | 0.39 kg |
Number of Main Contacts NO | 2 | Number of Main Contacts NC | 2 |
Number of Auxiliary Contacts NO | 0 | Number of Auxiliary Contacts NC | 0 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. | Rated Operational Voltage | Main Circuit 690 V |
Rated Frequency (f) | Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 55 A |
Rated Operational Current AC-1 (Ie) | (1000 V) 60 °C 45 A (690 V) 40 °C 55 A (690 V) 70 °C 37 A | Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 21.2 A (440 V) 60 °C 20 A (500 V) 60 °C 17.6 A (690 V) 60 °C 10.5 A (380 / 400 V) 60 °C 22 A (220 / 230 / 240 V) 60 °C 23.2 A |
Rated Operational Power AC-3 (Pe) | (400 V) 11 kW (415 V) 11 kW (440 V) 11 kW (500 V) 11 kW (690 V) 9 kW (220 / 230 / 240 V) 5.5 kW | Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 55 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 450 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Rated Control Circuit Voltage (Uc) | 50 Hz 24 ... 60 V 60 Hz 24 ... 60 V DC Operation 20 ... 60 V | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP10 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Terminal Type | Ring-Tongue Terminals | Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
General Use Rating UL/CSA | (600 V AC) 55 A | Tightening Torque UL/CSA | Control Circuit 11 in·lb Main Circuit 22 in·lb |
Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C | Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4758 >> Iec Contactors | Manufacturer ID | 1SBL296560R2100 |
Specifications may be subject to change without notice