Product Model
AF40B-22-00-13

Selling Points
- 1Operates with 100 to 250 VAC/VDC control voltages.
- 2Supports 11/18.5/22 kW coil power ratings.
- 3Ensures reliable operation with built-in surge suppression.
- 4Includes 2NO-2NC contact configuration for flexible control.
- 5Withstands short voltage dips and sags, ensuring consistent performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 70 mm | Product Net Depth / Length | 113.5 mm |
Product Net Height | 125.5 mm | Product Net Weight | 1.16 kg |
Number of Main Contacts NO | 2 | Number of Main Contacts NC | 2 |
Number of Auxiliary Contacts NO | 0 | Number of Auxiliary Contacts NC | 0 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1:22, CSA C22.2 No. 60947-4-1:22, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. | Rated Operational Voltage | Main Circuit 690 V |
Rated Frequency (f) | Control Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 105 A |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 70 A (690 V) 60 °C 60 A (690 V) 70 °C 50 A | Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 40 A (440 V) 60 °C 40 A (500 V) 60 °C 35 A (690 V) 60 °C 25 A (380 / 400 V) 60 °C 40 A (220 / 230 / 240 V) 60 °C 40 A |
Rated Operational Power AC-3 (Pe) | (415 V) 22 kW (440 V) 22 kW (500 V) 22 kW (690 V) 22 kW (380 / 400 V) 18.5 kW (220 / 230 / 240 V) 11 kW | Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A | Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V acc. to UL/CSA 600 V | Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V | Coil Consumption | Average Holding Value 50 / 60 Hz 4 V·A Average Holding Value DC 2 W |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 screws placed diagonally |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 4 ... 35 mm² Flexible with Insulated Ferrule 1/2x 4 ... 35 mm² Rigid Stranded 1/2x 6 ... 35 mm² | Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm² |
Wire Stripping Length | Auxiliary Circuit 0 mm Control Circuit 10 mm Main Circuit 16 mm | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 |
Terminal Type | Screw Terminals | Continuous Current Rating NEMA | 0 A |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V | General Use Rating UL/CSA | (600 V AC) 60 A |
Connecting Capacity Main Circuit UL/CSA | Rigid Stranded 1/2x 10-2 AWG | Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG Rigid Stranded 1/2x 18-14 AWG |
Tightening Torque UL/CSA | Control Circuit 11 in·lb Main Circuit 35 in·lb | Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C |
Climatic Withstand | Category B according to IEC 60947-1 Annex Q | Maximum Operating Altitude Permissible | Without Derating 3000 m |
Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B | Object Classification Code | Q |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
ETIM 9 | EC000066 - Power contactor, AC switching | eClass | V11.0 : 27371003 |
UNSPSC | 39121529 | Manufacturer ID | 1SBL347561R1300 |
Specifications may be subject to change without notice