Product Model
AF750-30-00-69

Selling Points
- 1Operates with 48 to 130 VAC/VDC, managing large control voltage variations.
- 2Minimizes panel energy consumption by up to 80%, allowing for smaller panel designs.
- 3Ensures reliable operation with built-in surge protection against short voltage dips and sags.
- 4Includes 3NO contacts and 1NO-1NC auxiliary contacts for flexible application.
- 5Features a block type design with pre-mounted auxiliary contacts and main circuit bars for easy extension with accessories.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 210 mm | Product Net Depth / Length | 242 mm |
Product Net Height | 283 mm | Product Net Weight | 13.6 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 0 | Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Main Circuit 1000 V | Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 1000 A (1000 V) 55 °C 875 A (1000 V) 70 °C 720 A (690 V) 40 °C 1050 A (690 V) 55 °C 875 A (690 V) 70 °C 720 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 750 A (440 V) 55 °C 750 A (500 V) 55 °C 750 A (690 V) 55 °C 650 A (1000 V) 55 °C 300 A (380 / 400 V) 55 °C 750 A (220 / 230 / 240 V) 55 °C 750 A | Rated Operational Power AC-3 (Pe) | (415 V) 425 kW (440 V) 450 kW (500 V) 520 kW (690 V) 600 kW (1000 V) 400 kW (380 / 400 V) 400 kW (220 / 230 / 240 V) 220 kW |
Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V | Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 1100 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 1100 V·A Pull-in at Max. Rated Control Circuit Voltage DC 1020 V·A |
Terminal Type | Main Circuit: Bars | NEMA Size | 7 |
Horsepower Rating NEMA | (230 V AC) Three Phase 300 Hp (460 V AC) Three Phase 600 Hp (575 V AC) Three Phase 600 Hp | Maximum Operating Voltage UL/CSA | Main Circuit 1000 V |
General Use Rating UL/CSA | (1000 V AC) 900 A (600 V AC) 900 A | Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 250 Hp (220 ... 240 V AC) Three Phase 300 Hp (440 ... 480 V AC) Three Phase 600 Hp (550 ... 600 V AC) Three Phase 700 Hp |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors | Manufacturer ID | 1SFL637001R6900 |
Specifications may be subject to change without notice