Product Model

AFC25-30-10-88

In Stock
Last updated: 2025/4/22
ABB AFC25-30-10-88

Selling Points

  • 1High-Voltage Capability: Controls power circuits up to 690V AC.
  • 2Block Type Design: Compact and efficient block type design for easy installation.
  • 3Built-in Auxiliary Contact: Includes 1 N.O built-in auxiliary contact for added functionality.
  • 4Screw Terminals: Equipped with screw terminals for secure connections.
  • 5IEC and UL Certification: Meets IEC and UL standards for safety and reliability.
Product Details
AFC25-30-10-88
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.303 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
0
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 35 A acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 32 A (690 V) 60 °C 32 A (690 V) 70 °C 28 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 25 A (380 / 400 V) 60 °C 25 A (220 / 230 / 240 V) 60 °C 25 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 25 A (380 / 400 V) 60 °C 25 A (220 / 230 / 240 V) 60 °C 25 A
Rated Operational Power AC-3 (Pe)
(415 V) 11 kW (380 / 400 V) 11 kW (220 / 230 / 240 V) 5.5 kW
Rated Operational Power AC-3e (Pe)
(415 V) 11 kW (380 / 400 V) 11 kW (220 / 230 / 240 V) 5.5 kW
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 85 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 105 A for 0.1 s 140 A for 1 s 100 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
Coil Consumption
Average Holding Value 50 / 60 Hz 8 V·A Average Pull-in Value 50 Hz 70 V·A Average Pull-in Value 60 Hz 66 V·A
Operate Time
Between Coil De-energization and NC Contact Closing 9 ... 20 ms Between Coil De-energization and NO Contact Opening 4 ... 18 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 30 A
Horsepower Rating UL/CSA
(120 V AC) Single Phase 2 hp (200 ... 208 V AC) Three Phase 7.5 hp (220 ... 240 V AC) Three Phase 7.5 hp (240 V AC) Single Phase 3 hp (440 ... 480 V AC) Three Phase 15 hp (550 ... 600 V AC) Three Phase 15 hp
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Manufacturer ID
1SBL211001R8810

Specifications may be subject to change without notice