Product Model
AFC96-30-11-80

Selling Points
- 1Controls power circuits up to 130 A (IEC AC-1) or 115 A UL general use.
- 2Features electromagnetic coil with control voltage range of 220-230 V AC 50 Hz / 230-240 V AC 60 Hz.
- 3Can be easily extended with add-on auxiliary contact blocks and a wide range of additional accessories.
- 4Part of the ABB EcoSolutionsTM portfolio, ensuring compliance with key performance indicators for environmental sustainability.
- 5Suitable for both IEC and UL applications, making it a versatile choice for various electrical control needs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 87 mm | Product Net Depth / Length | 119.5 mm |
Product Net Height | 116 mm | Product Net Weight | 1.25 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 1 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, CSA C22.2 No. 60947-1, CSA C22.2 No. 60947-4-1 | Rated Operational Voltage | Main Circuit 1000 V |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 130 A acc. to IEC 60947-5-1, Π= 40 °C 16 A | Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 130 A (690 V) 60 °C 105 A (690 V) 70 °C 90 A |
Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 96 A (440 V) 60 °C 96 A (500 V) 60 °C 80 A (690 V) 60 °C 57 A (380 / 400 V) 60 °C 96 A (220 / 230 / 240 V) 60 °C 96 A | Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 96 A (440 V) 60 °C 96 A (500 V) 60 °C 80 A (690 V) 60 °C 57 A (380 / 400 V) 60 °C 96 A (220 / 230 / 240 V) 60 °C 96 A |
Rated Operational Power AC-3 (Pe) | (415 V) 55 kW (440 V) 55 kW (500 V) 55 kW (690 V) 55 kW (380 / 400 V) 45 kW (220 / 230 / 240 V) 25 kW | Rated Operational Power AC-3e (Pe) | (415 V) 55 kW (440 V) 55 kW (500 V) 55 kW (690 V) 55 kW (380 / 400 V) 45 kW (220 / 230 / 240 V) 25 kW |
Rated Operational Power AC-6b (Pe) | (400 / 415 V) 40 °C, 50 / 60 Hz 60 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 53 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 60 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 75 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 75 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 70 kvar (690 V) 40 °C, 50 / 60 Hz 82 kvar (690 V) 55 °C, 50 / 60 Hz 82 kvar (690 V) 70 °C, 50 / 60 Hz 75 kvar | Rated Operational Current AC-15 (Ie) | (500 V) NC 2 |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 140 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 300 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1200 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 450 A for 0.1 s 140 A for 1 s 100 A | Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1150 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 750 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-15) 1200 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 1200 cycles per hour (DC-13) 900 cycles per hour | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 8 kV |
Maximum Mechanical Switching Frequency | 3600 cycles per hour | Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V 60 Hz 230 ... 240 V |
Coil Consumption | Average Holding Value 50 / 60 Hz 20 V·A Average Pull-in Value 50 Hz 236 V·A Average Pull-in Value 60 Hz 260 V·A | Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 21 ms Between Coil De-energization and NO Contact Opening 5 ... 16 ms Between Coil Energization and NC Contact Opening 3 ... 17 ms Between Coil Energization and NO Contact Closing 7 ... 22 ms |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | Mounting by Screws (not supplied) | 2 x M4 or 2 x M6 screws placed diagonally |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 6 ... 50 mm² Flexible with Insulated Ferrule 1/2x 6 ... 50 mm² Rigid 1x 6 ... 70 mm² Rigid 2x 6 ... 50 mm² Rigid 1x 6 ... 70 mm² Rigid 2x 6 ... 50 mm² | Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid 1/2x 1 ... 2.5 mm² | Wire Stripping Length | Control Circuit 10 mm Main Circuit 17 mm |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10 | Terminal Type | Screw Terminals |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V | General Use Rating UL/CSA | (600 V AC) 115 A |
Horsepower Rating UL/CSA | (120 V AC) Single Phase 7-1/2 hp (200 ... 208 V AC) Three Phase 30 hp (220 ... 240 V AC) Three Phase 40 hp (240 V AC) Single Phase 20 hp (440 ... 480 V AC) Three Phase 75 hp (550 ... 600 V AC) Three Phase 75 hp | Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb Main Circuit 53 in·lb |
Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C | Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: A 25 g Closed, Shock Direction: B1 25 g Closed, Shock Direction: B2 15 g Closed, Shock Direction: C1 25 g Closed, Shock Direction: C2 25 g Open, Shock Direction: B1 5 g |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors | Manufacturer ID | 1SBL401001R8011 |
Specifications may be subject to change without notice