Product Model
AX40-30-10-86

Selling Points
- 1Handles up to 65 A at 40°C ambient temperature.
- 2Rated for 690 V AC and 6 kV impulse withstand voltage.
- 3Front or side mounting options for auxiliary contact blocks.
- 4Operates at 400-415V (50Hz) and 415-440V (60Hz).
- 5Meets IEC 60947-4-1 and VDE 0110 (Gr. C) specifications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 54 mm | Product Net Depth / Length | 90 mm |
Product Net Height | 108.3 mm | Product Net Weight | 0.667 kg |
Number of Main Contacts NO | 3 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Number of Auxiliary Contacts NC | 0 |
Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V | Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 65 A acc. to IEC 60947-5-1, Π= 40 °C 16 A | Rated Operational Current AC-1 (Ie) | (220 / 240 V) 55 °C 60 A (690 V) 40 °C 60 A (690 V) 70 °C 42 A |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 40 A (440 V) 55 °C 37 A (500 V) 55 °C 33 A (690 V) 55 °C 25 A (380 / 400 V) 55 °C 40 A (220 / 230 / 240 V) 55 °C 40 A | Rated Operational Power AC-3 (Pe) | (415 V) 18.5 kW (440 V) 22 kW (500 V) 22 kW (690 V) 22 kW (380 / 400 V) 18.5 kW (220 / 230 / 240 V) 11 kW |
Rated Operational Current AC-15 (Ie) | (500 V) NC 2 (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A (400 / 440 V) 2 A | Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 65 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A for 0.1 s 140 A for 1 s 100 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A | Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-15) 1200 cycles per hour (AC-3) 1200 cycles per hour (DC-13) 900 cycles per hour |
Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (110 V) 0.55 A / 60 W (125 V) 1.1 A / 138 W (220 V) 0.55 A / 121 W (250 V) 0.55 A / 138 W (400 V) 2.8 A / 134 W (500 V) 2 A / 144 W | Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV | Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Rated Control Circuit Voltage (Uc) | 50 Hz 400 ... 415 V 60 Hz 415 ... 440 V | Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 14 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NC Contact Opening 6 ... 18 ms Between Coil Energization and NO Contact Closing 8 ... 21 ms |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | Terminal Type | Screw Terminals |
General Use Rating UL/CSA | (600 V AC) 60 A | Horsepower Rating UL/CSA | (120 V AC) Single Phase 3 hp (200 ... 208 V AC) Three Phase 10 hp (220 ... 240 V AC) Three Phase 15 hp (240 V AC) Single Phase 7.5 hp (440 ... 480 V AC) Three Phase 30 hp (550 ... 600 V AC) Three Phase 40 hp |
Tightening Torque UL/CSA | Auxiliary Circuit 9 in·lb Control Circuit 9 in·lb Main Circuit 20 in·lb | Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C |
Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II | Maximum Operating Altitude Permissible | Without Derating 3000 m |
Object Classification Code | Q | ETIM 7 | EC000066 - Power contactor, AC switching |
ETIM 8 | EC000066 - Power contactor, AC switching | ETIM 9 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors | Manufacturer ID | 1SBL321074R8610 |
Specifications may be subject to change without notice