Product Model
BC7-30-10-F-04

Selling Points
- 1Compact 3 pole design with flat pin connections.
- 2Ideal for residential, commercial, and industrial applications.
- 3Noiseless and hum-free coil for reliable operation.
- 4Integrated auxiliary contact for enhanced control.
- 5Suitable for loads up to 5.5 kW (AC-3) and 20 A / 690 V (AC-1).
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 52.5 mm | Product Net Height | 57.5 mm |
Product Net Depth / Length | 46.7 mm | Product Net Weight | 0.17 kg |
Number of Poles | 3 | Mini Contactor Type | Mini Contactor |
Rated Operational Voltage | Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC | Rated Frequency (f) | Control Circuit DC Main Circuit 50 Hz Main Circuit 60 Hz Main Circuit DC |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV Main Circuit 6 kV | Rated Insulation Voltage (Ui) | 690 V acc. to UL/CSA 600 V |
Number of Main Contacts NC | 0 | Number of Main Contacts NO | 3 |
Rated Operational Current AC-1 (Ie) | (220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A | Rated Operational Power AC-3 (Pe) | (230 V) Three Phase 3 kW (400 V) Three Phase 5.5 kW (500 V) Three Phase 5.5 kW (690 V) Three Phase, NO 3 kW |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A | Number of Auxiliary Contacts NC | 0 |
Number of Auxiliary Contacts NO | 1 | Rated Operational Current AC-15 (Ie) | (24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A | Conventional Free-air Thermal Current (Ith) | Main Circuit 20 A |
Rated Control Circuit Voltage (Uc) | 110 ... 125 V DC | Coil Operating Limits | (acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ⤠55 °C) |
Degree of Protection | Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20 | Mechanical Durability | 10000000 cycle |
Minimum Switching Capacity | Auxiliary Circuit 17 V Auxiliary Circuit 5 mA | Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | Power Loss | at Rated Operating Conditions AC-1 per Pole 1.4 W |
Standards | IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1 IEC 60335-2-40 A2L | Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Full Load Amps Motor Use | (115 V AC) Single Phase 13.8 A (200 V AC) Three Phase 7.8 A (220 ... 240 V AC) Three Phase 9.6 A (230 V AC) Single Phase 10 A (440 ... 480 V AC) Three Phase 7.6 A (550 ... 600 V AC) Three Phase 6.1 A | Horsepower Rating UL/CSA | (115 V AC) Single Phase 0.75 Hp (200 V AC) Three Phase 2 Hp (220 ... 240 V AC) Three Phase 3 Hp (230 V AC) Single Phase 1.5 Hp (440 ... 480 V AC) Three Phase 5 Hp (550 ... 600 V AC) Three Phase 5 Hp |
General Use Rating UL/CSA | (600 V AC) 16 A | Contact Rating UL/CSA | A600 |
Ambient Air Temperature | Operation -25 ... +55 °C Storage -40 ... +80 °C | Maximum Operating Altitude Permissible | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 15g | Resistance to Vibrations | 5g 5 ... 150 Hz |
Object Classification Code | Q | ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching | ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching | ETIM 8 | EC000066 - Power contactor, AC switching |
eClass | V11.0 : 27371003 | UNSPSC | 39121529 |
IDEA Granular Category Code (IGCC) | 4763 >> Power contactor, DC switching | Manufacturer ID | GJL1313003R0104 |
Specifications may be subject to change without notice