Product Model

CM-SRS.11P

In Stock
Last updated: 2025/4/19
ABB CM-SRS.11P

Selling Points

  • 1Precise Over- and Undercurrent Protection: Monitors currents from 3 mA to 15 A with adjustable hysteresis (3-30 %).
  • 2Compact Design: Measures just 22.5 mm wide, ideal for DIN rail mounting.
  • 3TRMS Measuring Principle: Ensures accurate measurements using the True Root Mean Square (TRMS) method.
  • 4Configurable Monitoring: Over- or undercurrent monitoring configurable to suit various applications.
  • 5Reliable Operation: Features a 1 c/o (SPDT) contact rated at 250 V / 4 A for reliable output switching.
Product Details
CM-SRS.11P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.137 kg
Function
Over- or undercurrent monitoring
Measuring Range
3 ... 30 mA 10 ... 100 mA 0.1 ... 1 A
Rated Control Supply Voltage (Us)
24 ... 240 V AC/DC
Output
1 c/o (SPDT) contact
Terminal Type
Screwless Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
24 V 10 mA
Rated Impulse Withstand Voltage (Uimp)
Measuring Circuit / Output Circuit 6 kV Output Circuit 1 / Output Circuit 2 4 kV Supply Circuit / Measuring Circuit 6 kV Supply Circuit / Output Circuit 4 kV
Rated Insulation Voltage (Ui)
Measuring Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 250 V Supply Circuit / Measuring Circuit 600 V Supply Circuit / Output Circuit 250 V
Degree of Protection
Housing IP50 Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
30000000 cycle
Connecting Capacity
Flexible with Ferrule 2x 0.5 ... 1.5 mm² Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² Flexible 2x 0.5 ... 1.5 mm² Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length
8 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 IEC/EN 63000 IEC/EN 60255-27 IEC/EN 61000-6-2 IEC/EN 61000-6-3 UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 2x 18-16 AWG Rigid 2x 20-16 AWG
Pilot Duty UL/CSA
B300
Flammability According to UL94
V-0
Ambient Air Temperature
Operation -20 ... +60 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Object Classification Code
B
ETIM 7
EC001440 - Current monitoring relay
ETIM 8
EC001440 - Current monitoring relay
ETIM 9
EC001440 - Current monitoring relay
eClass
V11.0 : 27371802
UNSPSC
39122332
E-Number (Finland)
2712300
E-Number (Norway)
4188047
E-Number (Sweden)
3860648
Manufacturer ID
1SVR740840R0200

Specifications may be subject to change without notice