Product Model

CM-TCN.011P

In Stock
Last updated: 2025/4/20
ABB CM-TCN.011P

Selling Points

  • 1Multi-Sensor Support: Measures temperatures with PT100, PT1000, PTC, NTC, and thermocouple sensors.
  • 2Configurable via LCD or App: Parametrize and configure the relay using the black-lit LCD or the ABB EPiC app.
  • 3Maintenance-Free Easy Connect Technology: Features push-in terminals for easy installation and reduced maintenance.
  • 4Wide Operating Range: Operates between -200°C and +850°C, suitable for various industrial applications.
  • 5Durable and Reliable: Rated for 100,000 cycles AC-12 and 30,000,000 cycles mechanical durability.
Product Details
CM-TCN.011P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
45 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.265 kg
Function
Overtemperature monitoring Undertemperature monitoring Over- and undertemperature monitoring
Measuring Range
-200 ... +850 °C
Sensor Type
PT100; PT1000; PTC; NTC; bimetal switch
Rated Control Supply Voltage (Us)
24 ... 240 V AC/DC
Rated Frequency (f)
Supply Circuit 50 Hz Supply Circuit 60 Hz Supply Circuit DC Hz
Output
3 x 1 c/o contacts, configurable
Terminal Type
Screwless Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
12 V 100 mA
Rated Impulse Withstand Voltage (Uimp)
Measuring Circuit / Output Circuit 6 kV Output Circuit 1 / Output Circuit 2 4 kV Supply Circuit / Measuring Circuit 6 kV Supply Circuit / Output Circuit 6 kV
Rated Insulation Voltage (Ui)
Measuring Circuit / Output Circuit 600 V Output Circuit 1 / Output Circuit 2 300 V Supply Circuit / Measuring Circuit 600 V Supply Circuit / Output Circuit 600 V
Degree of Protection
Housing IP50 Terminals IP20
Overvoltage Category
III
Pollution Degree
2
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
30000000 cycle
Connecting Capacity
Flexible with Ferrule 2x 0.5 ... 1.5 mm² Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² Flexible 2x 0.5 ... 1.5 mm² Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length
8 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 2x 18-16 AWG Rigid 2x 20-16 AWG
Pilot Duty UL/CSA
B300
Ambient Air Temperature
Operation -25 ... +60 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Object Classification Code
B
ETIM 7
EC001446 - Temperature monitoring relay
ETIM 8
EC001446 - Temperature monitoring relay
ETIM 9
EC001446 - Temperature monitoring relay
eClass
V11.0 : 27371810
UNSPSC
39122331
E-Number (Norway)
4187798
Manufacturer ID
1SVR760740R0110

Specifications may be subject to change without notice