Product Model

CT-MVS.22P

In Stock
Last updated: 2025/4/20
ABB CT-MVS.22P

Selling Points

  • 1The CT-MVS.22P provides 11 timing functions and 10 time ranges from 0.05 s to 300 h.
  • 2Features tool-free push-in terminals for quick and easy installation.
  • 3Designed with a sealable transparent cover for protection against unauthorized changes.
  • 4Operates with a rated control supply voltage of 24 - 48 V DC / 24 - 240 V AC.
  • 5Meets high standards with a housing material classified UL 94 V-0 for fire protection and IP50/20 protection against dust and moisture.
Product Details
CT-MVS.22P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.131 kg
Timer Relay Type
Impulse OFF Impulse ON OFF-Delay ON-Delay Star-Delta
Time Range
0.05 s ... 300 h
Rated Control Supply Voltage (Us)
24 ... 240 V AC 24 ... 48 V DC
Rated Operational Voltage
Auxiliary Circuit 250 V
Rated Frequency (f)
50 / 60 Hz DC
Output
2 c/o (SPDT) contacts
Terminal Type
Screwless Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
12 V 100 mA
Rated Impulse Withstand Voltage (Uimp)
Input Circuit 4 kV Output Circuit 1 / Output Circuit 2 4 kV
Rated Insulation Voltage (Ui)
Input Circuit / Output Circuit 500 V Output Circuit 1 / Output Circuit 2 300 V
Degree of Protection
Housing IP50 Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
30000000 cycle
Connecting Capacity
Flexible with Ferrule 2x 0.5 ... 1.5 mm² Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² Flexible 2x 0.5 ... 1.5 mm² Rigid 2x 0.5 ... 1.5 mm²
Wire Stripping Length
8 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 IEC/EN 63000 IEC/EN 61812-1 UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 2x 18-16 AWG Rigid 2x 20-16 AWG
Pilot Duty UL/CSA
B300
Flammability According to UL94
V-0
Ambient Air Temperature
Operation -25 ... +60 °C Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Object Classification Code
K
ETIM 7
EC001439 - Timer relay
ETIM 8
EC001439 - Timer relay
ETIM 9
EC001439 - Timer relay
eClass
V11.0 : 27371605
UNSPSC
39122329
E-Number (Finland)
2712217
E-Number (Norway)
4187933
E-Number (Sweden)
4033129
Manufacturer ID
1SVR740020R3300

Specifications may be subject to change without notice