Product Model

DDA804 A S-100/1

In Stock
Last updated: 2025/4/18
ABB DDA804 A S-100/1

Selling Points

  • 1High Protection Against Earth Fault Currents: The DDA804 A S-100/1 provides robust protection against indirect contacts and direct contacts, ensuring safety in various environments.
  • 2Intentional Tripping Delay: This feature allows for selective tripping, ensuring that only the faulty circuit is disconnected while maintaining power to other circuits.
  • 34-Pole Configuration: Designed with four poles, this device supports multiple connections, enhancing flexibility in electrical installations.
  • 4Rated Current of 100 A: With a nominal current of 100 A, it can handle significant electrical loads, making it suitable for various applications.
  • 5Compliance with IEC/EN Standards: Meets stringent IEC/EN 60947-2 and IEC/EN 61009 standards, ensuring high-quality performance and reliability.
Product Details
DDA804 A S-100/1
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Standards
IEC EN 60947-2 Ann. B
Type of Residual Current
Type A
Suitable For
S800S S800N S800C S800B
Rated Voltage (Ur)
230/400 V AC 240/415 V AC 400/690 V AC
Rated Operational Voltage
400/690 V
Rated Insulation Voltage (Ui)
690 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Rated Current (In)
100 A
Rated Residual Current
1000 mA
Maximum Surge Current
5 kA
Leakage Current Type
A
Rated Frequency (f)
50 … 60 Hz
Power Loss
10.5 W
Number of Poles
4
Operating Characteristic
Selective
Connecting Capacity
Rigid 6 … 50 mm² Flexible 6 … 70 mm²
Ambient Temperature
-25...60 °C
Ambient Air Temperature
Operation -25...60 °C
Degree of Protection
IP2X
Environmental Information
refer to RoHS information
Short-Circuit Current Rating (SCCR)
1...1 A
Width in Number of Modular Spacings
6.5
Product Net Width
117 mm
Product Net Height
108.2 mm
Product Net Depth / Length
82.3 mm
Product Net Weight
460 g
ETIM 8
EC002297 - Residual current circuit breaker (RCCB) module
ETIM 9
EC002297 - Residual current circuit breaker (RCCB) module
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Business
CN8
85363030
eClass
V11.0 : 27142210
Object Classification Code
F
Manufacturer ID
2CSB804201R5000

Specifications may be subject to change without notice