Product Model
DDA804 A S-100/1

Selling Points
- 1High Protection Against Earth Fault Currents: The DDA804 A S-100/1 provides robust protection against indirect contacts and direct contacts, ensuring safety in various environments.
- 2Intentional Tripping Delay: This feature allows for selective tripping, ensuring that only the faulty circuit is disconnected while maintaining power to other circuits.
- 34-Pole Configuration: Designed with four poles, this device supports multiple connections, enhancing flexibility in electrical installations.
- 4Rated Current of 100 A: With a nominal current of 100 A, it can handle significant electrical loads, making it suitable for various applications.
- 5Compliance with IEC/EN Standards: Meets stringent IEC/EN 60947-2 and IEC/EN 61009 standards, ensuring high-quality performance and reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Standards | IEC EN 60947-2 Ann. B | Type of Residual Current | Type A |
Suitable For | S800S S800N S800C S800B | Rated Voltage (Ur) | 230/400 V AC 240/415 V AC 400/690 V AC |
Rated Operational Voltage | 400/690 V | Rated Insulation Voltage (Ui) | 690 V |
Rated Impulse Withstand Voltage (Uimp) | 6 kV | Rated Current (In) | 100 A |
Rated Residual Current | 1000 mA | Maximum Surge Current | 5 kA |
Leakage Current Type | A | Rated Frequency (f) | 50 ⦠60 Hz |
Power Loss | 10.5 W | Number of Poles | 4 |
Operating Characteristic | Selective | Connecting Capacity | Rigid 6 ⦠50 mm² Flexible 6 ⦠70 mm² |
Ambient Temperature | -25...60 °C | Ambient Air Temperature | Operation -25...60 °C |
Degree of Protection | IP2X | Environmental Information | refer to RoHS information |
Short-Circuit Current Rating (SCCR) | 1...1 A | Width in Number of Modular Spacings | 6.5 |
Product Net Width | 117 mm | Product Net Height | 108.2 mm |
Product Net Depth / Length | 82.3 mm | Product Net Weight | 460 g |
ETIM 8 | EC002297 - Residual current circuit breaker (RCCB) module | ETIM 9 | EC002297 - Residual current circuit breaker (RCCB) module |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | WEEE B2C / B2B | Business To Business |
CN8 | 85363030 | eClass | V11.0 : 27142210 |
Object Classification Code | F | Manufacturer ID | 2CSB804201R5000 |