Product Model
DS201 B10 G30

Selling Points
- 1High-Performance Protection: Safeguards single-phase circuits against overload and short-circuit currents.
- 2Compact Design: Two-module width for easy DIN rail mounting.
- 3Advanced Sensitivity: 30 mA trip sensitivity for precise fault detection.
- 4Durable Construction: Built to withstand harsh environmental conditions (-25°C to 55°C).
- 5Comprehensive Compliance: Meets IEC 61009-1 and EN 61009-1 standards for reliability and safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Standards | IEC/EN 61009-1 IEC/EN 61009-2-1 OVE E 8601 | Tripping Characteristic | B |
Type of Residual Current | Type A/G | Rated Operational Voltage | acc. to IEC 60898-1 230 V |
Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 500 V | Test Voltage (Ut) | 170 ... 264 V |
Rated Impulse Withstand Voltage (Uimp) | 4 kV | Dielectric Test Voltage | 2 kV |
Input Voltage Type | AC | Rated Current Sensitivity | 0.03 A |
Rated Current (In) | 10 A | Rated Residual Operating Current (IÎn) | 6000 A |
Rated Residual Current | 30 mA | Rated Short-Circuit Capacity | 6 kA |
Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 10 kA | Rated Service Short-Circuit Breaking Capacity (Ics) | 7.5 kA |
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 6 kA | Maximum Surge Current | 3 kA |
Rated Frequency (f) | 50 ⦠60 Hz | Power Loss | Average per Pole 1.2 W Phase Pole 1.8 W Neutral Pole 0.5 W Total 2.3 W |
Power Supply Connection | Arbitrary | Contact Position Indication | Red ON / Green OFF |
Energy Limiting Class | 3 | Electrical Endurance | 10000 cycle |
Mechanical Endurance | 20000 cycle | Number of Protected Poles | 1 |
Number of Poles | 1+N | Number of Modular Spacings per DIN Rail | 2 |
Fault Indication | Blue flag on toggle | Operating Characteristic | Instantaneous |
Overvoltage Category | III | Position of Neutral Terminals | Right |
Tightening Torque | 1.2 N·m | Accessory Type | Auxiliary contact, Signal contact / auxiliary contact, Shunt trip, Auxiliary contact for bottom fitting, Overvoltage release, Motor operating device |
Actuator Type | Toggle - Insulation group II, Black RAL 9005,
sealable in ON-OFF positions | Earthing Switch Type | Short-Time Delayed |
Housing Type | Insulation group I - II, RAL 7035 | Mounting Type | DIN-Rail |
Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal | Mounting Position | Any |
Accessories Available | Yes | Connecting Capacity | Busbar 10/10 mm² Rigid 0.75 ⦠25 mm² Flexible 0.75 ⦠16 mm² |
Rated Cross-Section | 1 - Solid-Core 0.75 ⦠25 mm² 4 - Multi-Wired 0.75 ⦠16 mm² | Wire Stripping Length | 10 mm |
Terminal Type | Screw Terminals | Ambient Air Temperature | Operation -25 ⦠55 °C |
Reference Ambient Air Temperature | 30 °C | Degree of Protection | IP20 |
Pollution Degree | 2 | Environmental Conditions | 28 cycles with 55 °C / 90-96 % and 25 °C / 95-100 % |
Resistance to Vibrations | 20 Cycles with Load 0.8 In: 1g or 1mm 50 ⦠150 ⦠5 Hz | Resistance to Shock acc. to IEC 60068-2-27 | 25g 2 shocks 13 ms |
Environmental Information | 2CSC422002K2701 | Width in Number of Modular Spacings | 2 |
Product Net Width | 35 mm | Product Net Height | 85 mm |
Product Net Depth / Length | 69 mm | Product Net Weight | 200 g |
Built-In Depth (t2) | 35 mm | ETIM 8 | EC000905 - Earth leakage circuit breaker |
ETIM 9 | EC000905 - Earth leakage circuit breaker | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
WEEE B2C / B2B | Business To Consumer | CN8 | 85363010 |
eClass | V11.0 : 27142207 | Object Classification Code | F |
Manufacturer ID | 2CSR255482R1105 |
Specifications may be subject to change without notice