Product Model
F204 A-125/0.03-L

Selling Points
- 1Provides reliable protection against smooth d.c. earth fault currents, ensuring safety in installations.
- 2Designed for DIN rail mounting, this RCD operates efficiently with a power loss of 7.5 W per pole at rated conditions.
- 3Features an instantaneous operating characteristic, ensuring quick response to fault currents.
- 4Compact dimensions (0.072 m width, 0.085 m height, 0.069 m depth) make it ideal for space-constrained installations.
- 5Meets IEC/EN 61008 standards, ensuring compliance with international safety regulations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Standards | IEC/EN 61008 | Type of Residual Current | Type A |
Rated Voltage (Ur) | 230/400 V | Rated Operational Voltage | 230 / 400 V AC |
Rated Insulation Voltage (Ui) | 500 V | Test Voltage (Ut) | 250-440 V |
Rated Impulse Withstand Voltage (Uimp) | 4 kV | Input Voltage Type | AC |
Rated Current (In) | 125 A | Rated Residual Current | 30 mA |
Rated Conditional Short-Circuit Current (Inc) | 10 kA | Leakage Current Type | A |
Frequency (f) | 50/60 Hz | Rated Frequency (f) | 50 Hz |
Power Loss | at Rated Operating Conditions per Pole 7.5 W | Power Supply Connection | Arbitrary |
Electrical Endurance | 10000 cycle | Number of Poles | 4 |
Number of Modular Spacings per DIN Rail | 4 | Operating Characteristic | Instantaneous |
Position of Neutral Terminals | Left | Tightening Torque | 2.8 N·m |
Accessory Type | Signal/Auxiliary contact Motor operating device | Mounting Type | DIN-Rail |
Options Provided | None | Mounting Position | Any |
Accessories Available | Yes | Connecting Capacity | Busbar 10 mm² Rigid 35 ... 35 mm² Flexible 35 ... 35 mm² |
Rated Cross-Section | 4 - Multi-Wired 0...25 mm² 1 - Solid-Core 35...35 mm² | Wire Stripping Length | 12 mm |
Terminal Type | Screw Terminals | Ambient Air Temperature | Operation -25 ... 40 °C Storage -40 ... 70 °C |
Degree of Protection | IP2X | Pollution Degree | 2 |
Environmental Information | Refer to RoHS | Short-Circuit Current Rating (SCCR) | 30 mA |
Width in Number of Modular Spacings | 4 | Product Net Width | 72 mm |
Product Net Height | 85 mm | Product Net Depth / Length | 69.5 mm |
Product Net Weight | 500 g | Built-In Depth (t2) | 69 mm |
ETIM 8 | EC000003 - Residual current circuit breaker (RCCB) | ETIM 9 | EC000003 - Residual current circuit breaker (RCCB) |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | WEEE B2C / B2B | Business To Consumer |
CN8 | 85363030 | UNSPSC | 39121601 |
eClass | V11.0 : 27142201 | IDEA Granular Category Code (IGCC) | 4875 >> Residual current circuit breaker (RCCB) |
Object Classification Code | F | Manufacturer ID | 2CSF204123R1950 |
Specifications may be subject to change without notice