ABB F204AS-125/0.3L

Selling Points

  • 1Advanced Earth Leakage Protection: Ensures safety against fault currents to earth.
  • 2DIN Rail Mounting: Convenient and space-efficient installation.
  • 3High Current Rating: Supports up to 125A, suitable for heavy-duty applications.
  • 4Instantaneous Break Time: Rapid tripping for immediate fault detection.
  • 5International Standards Compliance: Manufactured according to international safety standards.
Product Details
F204AS-125/0.3L
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Type of Residual Current
Type A
Rated Voltage (Ur)
230/400 V
Rated Operational Voltage
230 / 400 V AC
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 500 V
Test Voltage (Ut)
200-440 V
Rated Impulse Withstand Voltage (Uimp)
4 kV
Input Voltage Type
AC
Rated Current (In)
125 A
Rated Conditional Short-Circuit Current (Inc)
10 kA
Frequency (f)
50/60 Hz
Rated Frequency (f)
50 Hz
Power Loss
at Rated Operating Conditions per Pole 7.5 W
Number of Poles
4
Number of Modular Spacings per DIN Rail
4
Operating Characteristic
Selective
Tightening Torque
2.8 N·m
Accessory Type
Signal/Auxiliary contact Motor operating device
Mounting Type
DIN-Rail
Options Provided
None
Mounting Position
Any
Accessories Available
Yes
Rated Cross-Section
1 - Solid-Core 1.5 ... 50 mm²
Wire Stripping Length
12 mm
Terminal Type
Screw Terminals
Ambient Air Temperature
Operation -25 ... 40 °C Storage -40 ... 70 °C
Degree of Protection
IP20
Pollution Degree
2
Resistance to Vibrations
20 Cycles with Load 0.8 In: 1g or 1mm 50 … 150 … 5 Hz
Resistance to Shock acc. to IEC 60068-2-27
25g 2 shocks 13 ms
Width in Number of Modular Spacings
4
Product Net Width
72 mm
Product Net Height
85 mm
Product Net Depth / Length
69.5 mm
Product Net Weight
500 g
Built-In Depth (t2)
69 mm
ETIM 8
EC000003 - Residual current circuit breaker (RCCB)
ETIM 9
EC000003 - Residual current circuit breaker (RCCB)
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Consumer
CN8
85363030
eClass
V11.0 : 27142201
IDEA Granular Category Code (IGCC)
4875 >> Residual current circuit breaker (RCCB)
Object Classification Code
Q
Manufacturer ID
2CSF204223R3950