Selling Points

  • 1High-Performance DC Contactor: Suitable for DC-1 applications with a wide control voltage range of 48-130V.
  • 2Wide Operating Voltage: Operates at 48-130V AC/DC, ensuring flexibility in various industrial settings.
  • 3High Current Capacity: Handles up to 1050A, making it reliable for heavy-duty applications.
  • 4Durable Design: Meets IEC 60529 and IEC 60947-1 standards for protection and insulation, ensuring long-lasting performance.
  • 5Versatile Connectivity: Features 3 main contacts (NO) and 1 auxiliary contact (NC) for versatile circuit configurations.
Product Details
GAF750-10-11-69
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product Net Width
210 mm
Product Net Depth / Length
242 mm
Product Net Height
283 mm
Product Net Weight
14 kg
Number of Main Contacts NO
1
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1050 A
Rated Operational Current DC-1 (Ie)
(1000 V) 3 Poles in Series, 40 °C 1050 A (1000 V) 3 Poles in Series, 55 °C 875 A (1000 V) 3 Poles in Series, 70 °C 720 A (220 V) 3 Poles in Series, 40 °C 1050 A (220 V) 3 Poles in Series, 55 °C 875 A (220 V) 3 Poles in Series, 70 °C 720 A (400 V) 3 Poles in Series, 40 °C 1050 A (400 V) 3 Poles in Series, 55 °C 875 A (400 V) 3 Poles in Series, 70 °C 720 A (600 V) 3 Poles in Series, 40 °C 1050 A (600 V) 3 Poles in Series, 55 °C 875 A (600 V) 3 Poles in Series, 70 °C 720 A
Rated Insulation Voltage (Ui)
acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
3 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V 60 Hz 48 ... 130 V DC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A Holding at Max. Rated Control Circuit Voltage DC 4.5 W Pull-in at Max. Rated Control Circuit Voltage 50 Hz 850 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 850 V·A Pull-in at Max. Rated Control Circuit Voltage DC 950 V·A
Connecting Capacity Main Circuit
Bar 52 mm² Rigid Al-Cable 3x185 mm² Rigid Cu-Cable 300 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(1000 V DC) 900 A (440 V DC) 900 A (600 V DC) 900 A
Ambient Air Temperature
Operation -40 ... 70 °C Storage -40 ... +70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 g Shock Direction: B1 5 g Shock Direction: B2 5 g Shock Direction: C1 5 g Shock Direction: C2 5 g
Object Classification Code
Q
ETIM 7
EC002552 - Power contactor, DC switching
ETIM 8
EC002552 - Power contactor, DC switching
ETIM 9
EC002552 - Power contactor, DC switching
eClass
V11.0 : 27371018
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
Manufacturer ID
1SFL637025R6911

Specifications may be subject to change without notice