Product Model
MS132-0.4B

Selling Points
- 1Compact design for space-saving installations.
- 2High reliability with short-circuit service breaking capacities up to 100 kA.
- 3Adjustable current setting for customizable overload protection.
- 4Phase loss sensitivity and trip-free mechanism for enhanced safety.
- 5Suitable for three-phase applications with screw terminals and rotary handle control.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 45 mm | Product Net Height | 90 mm |
Product Net Depth / Length | 86.75 mm | Product Net Weight | 0.215 kg |
Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 100 kA (250 V DC) 3 Poles in Series 10 kA (400 V AC) 100 kA (440 V AC) 100 kA (500 V AC) 100 kA (690 V AC) 100 kA | Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 100 kA (400 V AC) 100 kA (440 V AC) 100 kA (500 V AC) 100 kA (690 V AC) 100 kA |
Rated Instantaneous Short-Circuit Current Setting (Ii) | 5 A | Setting Range | 0.25 ... 0.40 A |
Rated Operational Power AC-3 (Pe) | (400 V) Three Phase 0.09 kW | Rated Operational Power AC-3e (Pe) | (400 V) Three Phase 0.09 kW |
Rated Operational Voltage | Main Circuit 690 V AC Main Circuit 250 V DC | Rated Operational Current (Ie) | 0.4 A |
Rated Operational Current AC-3 (Ie) | 0.4 A | Rated Operational Current AC-3e (Ie) | 0.4 A |
Rated Operational Current DC-5 (Ie) | 0.4 A | Rated Frequency (f) | Main Circuit 50 Hz Main Circuit 60 Hz |
Operating Frequency (fsw) | 0 ... 400 Hz | Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
Rated Insulation Voltage (Ui) | 690 V | Power Loss | at Rated Operating Conditions per Pole 0.6 ... 1.7 W |
Number of Poles | 3 | Conventional Free-air Thermal Current (Ith) | Main Circuit 0.4 A |
Degree of Protection | Housing IP20 Main Circuit Terminals IP10 | Pollution Degree | 3 |
Electrical Durability | 50000 cycle | Mechanical Durability | 100000 cycle |
Terminal Type | Screw Terminals | Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm² Flexible 1/2x 0.75 ... 2.5 mm² Rigid 1/2x 1 ... 4 mm² |
Tightening Torque | Main Circuit 0.8 ... 1.2 N·m | Wire Stripping Length | Main Circuit 9 mm |
Recommended Screw Driver | Pozidriv 2 | Mounting Position | 1 ... 6 |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | Minimum Mounting Distance | Electrical Conductive Board, Horizontal - Up to 400 V 0 mm Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm Electrical Conductive Board, Vertical 75 mm Other Device Same Type, Horizontal 0 mm Other Device Same Type, Vertical 150 mm |
Actuator Type | Rotary Handle | Contact Position Indication | ON / OFF / TRIP |
Standards | IEC 60077-1 (applicable parts) IEC 60077-2 (applicable parts) IEC/EN 60947-1 IEC/EN 60947-2 IEC/EN 60947-4-1 | Remarks | UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx |
Short-Circuit Current Rating (SCCR) | Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 65 kA Manual Self-Protected Combination Controllers (Type E), (600Y / 347 V AC) 47 kA Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 65 kA Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 47 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 65 kA Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 47 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA | Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
Full Load Amps Motor Use | (200 V AC) Three Phase 0.4 A (208 V AC) Three Phase 0.4 A (220 ... 240 V AC) Three Phase 0.4 A (440 ... 480 V AC) Three Phase 0.4 A (550 ... 600 V AC) Three Phase 0.4 A | Locked Rotor Amps | (200 V AC) Three Phase 2.4 A (208 V AC) Three Phase 2.4 A (220 ... 240 V AC) Three Phase 2.4 A (440 ... 480 V AC) Three Phase 2.4 A (550 ... 600 V AC) Three Phase 2.4 A |
General Use Rating UL/CSA | (600 V AC) 0.4 A | Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-12 AWG Stranded 1/2x 16-12 AWG |
Tightening Torque UL/CSA | Main Circuit 10 ... 12 in·lb | Ambient Air Temperature | Around the Enclosure 0 ... +40 °C Operation -25 ... +70 °C Operation Compensated -25 ... +60 °C Storage -50 ... +80 °C |
Ambient Air Temperature Compensation | Yes | Maximum Operating Altitude Permissible | 2000 m |
Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g | Resistance to Vibrations | 5g 3 ... 150 Hz |
Shock and Vibration Withstand acc. to IEC 61373 | Category 1, Class B | Object Classification Code | F |
ETIM 5 | EC000074 - Motor protective circuit-breaker | ETIM 6 | EC000074 - Motor protection circuit-breaker |
ETIM 7 | EC000074 - Motor protection circuit-breaker | ETIM 8 | EC000074 - Motor protection circuit-breaker |
eClass | V11.0 : 27370401 | UNSPSC | 39121521 |
IDEA Granular Category Code (IGCC) | 4731 >> Manual Starters | Manufacturer ID | 1SAM350200R1003 |
Specifications may be subject to change without notice