Product Model
NFC22EK-86

Selling Points
- 1Highly Reliable Performance: Designed to meet IEC and UL standards for reliable operation in various environments.
- 2Versatile Connectivity: Equipped with screw terminals for easy connection and flexible wiring options.
- 3Efficient Power Switching: Ideal for switching auxiliary and control circuits with optimized operating time.
- 4Durable Construction: Built to withstand climatic conditions and vibrations according to IEC 60947-1 Annex Q.
- 5Comprehensive Accessory Range: Compatible with a wide range of accessories including timers, interlocking units, and surge suppressors.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 45 mm | Product Net Depth / Length | 77 mm |
Product Net Height | 92.3 mm | Product Net Weight | 0.306 kg |
Number of Main Contacts NO | 0 | Number of Main Contacts NC | 0 |
Number of Auxiliary Contacts NO | 2 | Number of Auxiliary Contacts NC | 2 |
Standards | IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60947-1, UL 60947-5-1, CSA C22.2 No. 60947-1-13, CSA C22.2 No. 60947-5-1-14 | Rated Operational Voltage | Auxiliary Circuit 690 V Main Circuit 690 V |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz Main Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Π= 40 °C 16 A |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A | Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A |
Maximum Electrical Switching Frequency | (AC-1) 0 cycles per hour (AC-15) 1200 cycles per hour (AC-2 / AC-4) 0 cycles per hour (AC-3) 0 cycles per hour (DC-13) 900 cycles per hour | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 6 kV Auxiliary Circuit 6 kV |
Maximum Mechanical Switching Frequency | 6000 cycles per hour | Rated Control Circuit Voltage (Uc) | 50 Hz 400 ... 415 V 60 Hz 415 ... 440 V |
Coil Consumption | 2.3 W | Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 20 ms Between Coil De-energization and NO Contact Opening 4 ... 18 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms Between Coil Energization and NO Contact Closing 10 ... 26 ms |
Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² Flexible 1/2x 0.5 ... 2.5 mm² Rigid 1/2x 1 ... 2.5 mm² | Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² Flexible 1/2x 0.5 ... 2.5 mm² Rigid 1/2x 1 ... 2.5 mm² |
Wire Stripping Length | Auxiliary Circuit 10 mm Control Circuit 10 mm | Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Terminal Type | Push-in Spring Terminals | Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... 60 °C Close to Contactor without Thermal O/L Relay -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +60 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C | Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
Object Classification Code | K | ETIM 7 | EC000196 - Contactor relay |
ETIM 8 | EC000196 - Contactor relay | ETIM 9 | EC000196 - Contactor relay |
eClass | V11.0 : 27371001 | UNSPSC | 39121500 |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors | Manufacturer ID | 1SBH131005R8622 |
Specifications may be subject to change without notice