Product Model
NFZ33/11-20

Selling Points
- 1Wide Control Voltage Range: Operates between 12-20V DC, suitable for various industrial applications.
- 2High Reliability: Built-in surge protection and compliance with IEC 60947-5-1 and UL 508 standards.
- 3Compact Design: Dimensions: 45mm width, 86mm height, and 110.5mm depth, making it ideal for DIN rail mounting.
- 4Multiple Contacts: Features 8-pole configuration with 4 NC and 4 NO contacts for versatile circuit control.
- 5Durable Construction: Meets IEC 60529 and EN 60529 standards for IP20 protection, ensuring robust performance in harsh environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Product Net Width | 45 mm | Product Net Depth / Length | 110.5 mm |
Product Net Height | 86 mm | Product Net Weight | 0.34 kg |
Number of Auxiliary Contacts NO | 4 | Number of Auxiliary Contacts NC | 4 |
Standards | IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14-13 | Rated Operational Voltage | Auxiliary Circuit 690 V |
Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz | Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Π= 40 °C 16 A |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A | Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A for 1 s 100 A |
Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour (DC-13) 900 cycles per hour | Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V | Rated Impulse Withstand Voltage (Uimp) | 6 kV |
Maximum Mechanical Switching Frequency | 6000 cycles per hour | Rated Control Circuit Voltage (Uc) | DC Operation 12 ... 20 V |
Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms | Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally | Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² Rigid Solid 1/2x 1 ... 2.5 mm² Rigid Stranded 1/2x 1 ... 2.5 mm² | Wire Stripping Length | Auxiliary Circuit 10 mm Control Circuit 10 mm |
Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | Terminal Type | Screw Terminals |
Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG Rigid Stranded 1/2x 18-14 AWG | Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb |
Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C | Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
Maximum Operating Altitude Permissible | Without Derating 3000 m | Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g Closed, Shock Direction: B2 15 g Open, Shock Direction: B1 5 g Shock Direction: A 30 g Shock Direction: B2 15 g Shock Direction: C1 25 g |
Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz | Object Classification Code | K |
ETIM 7 | EC000196 - Contactor relay | ETIM 8 | EC000196 - Contactor relay |
ETIM 9 | EC000196 - Contactor relay | eClass | V11.0 : 27371001 |
UNSPSC | 39121500 | Manufacturer ID | 1SBH136001R2039 |
Specifications may be subject to change without notice