Product Model
OS400D11

Selling Points
- 1Front-operated design for easy handling.
- 22-pole configuration suitable for various industrial settings.
- 3Compliant with DIN standards for reliability and consistency.
- 4Compact dimensions (190 mm x 230 mm x 193 mm) for space efficiency.
- 5Handle and shaft not included, ensuring flexibility in installation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Pollution Degree | 3 | Product Net Width | 190 mm |
Product Net Height | 230 mm | Product Net Depth / Length | 193 mm |
Product Net Weight | 5.1 kg | Cable Cross-Section | 2.5 ... 25 mm² |
Conventional Free-air Thermal Current (Ith) | Π= 40 °C 400 A | Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
Fuse Size | NH0 NH1 NH2 | Fuse System | DIN |
Handle Type | Handle and shaft not included | Mounting Type | Base mounting |
Number of Poles | 2 | Operating Mode | Front Operated |
Pollution Degree | 3 | Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
Power Loss | at Rated Operating Conditions per Pole 30 W | Rated Conditional Short-Circuit Current (Inc) | (690 V) 80 kA |
Rated Current (In) | Main Circuit 400 A | Rated Impulse Withstand Voltage (Uimp) | 12 kV |
Rated Insulation Voltage (Ui) | 1000 V | Rated Operational Current AC-21A (Ie) | (500 V) 400 A (690 V) 400 A |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A (500 V) 400 A (690 V) 400 A |
Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 132 kW (400 V) 220 kW (415 V) 230 kW (500 V) 280 kW (690 V) 400 kW | Rated Operational Voltage | Main Circuit 690 V AC |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 14 kiloampere rms | Standards | IEC 60947-3 |
Switches Operating Mechanism | 11 (Between the Poles) | Terminal Type | Lug terminals |
Terminal Width | 25 mm | Tightening Torque | 30 ... 44 N·m |
Tightening Torque | 30 ... 44 N·m | Object Classification Code | Q |
ETIM 8 | EC001040 - Fuse switch disconnector | ETIM 9 | EC001040 - Fuse switch disconnector |
UNSPSC | 39122233 | IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
eClass | V11.1 : 27371401 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SCA110201R1001 |
Specifications may be subject to change without notice