Product Model
OS630B22N1

Selling Points
- 1Designed for consistent operation in demanding industrial environments.
- 2Meets British Standard specifications for switch fuses.
- 3Easy to use with a front-operated mechanism for quick switching.
- 4Suitable for various electrical configurations with a 4-pole setup.
- 5Built with robust materials to withstand heavy use and harsh conditions.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Pollution Degree | 3 | Product Net Width | 429 mm |
Product Net Height | 306 mm | Product Net Depth / Length | 233 mm |
Product Net Weight | 18.464 kg 40.71 lb | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 630 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 570 A | Fourth Pole Position | Left Side |
Fourth Pole Type | Switched - With Solid Link | Fuse Size | C1-C2 |
Fuse System | British Standard | Handle Type | Handle and shaft not included |
Mounting Type | Base mounting | Number of Poles | 4 |
Operating Mode | Front Operated | Pollution Degree | 3 |
Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out | Power Loss | at Rated Operating Conditions per Pole 46 W |
Rated Conditional Short-Circuit Current (Inc) | (690 V) 80 kA | Rated Current (In) | Main Circuit 630 A |
Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Current AC-21A (Ie) | (500 V) 630 A (690 V) 630 A | Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A |
Rated Operational Current AC-23A (Ie) | (500 V) 630 A (380 ... 415 V) 630 A (690 V) 630 A | Rated Operational Current AC-23B (Ie) | (380 ... 415 V) 630 A (500 V) 630 A (690 V) 630 A |
Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 200 kW (400 V) 355 kW (415 V) 355 kW (500 V) 450 kW (690 V) 630 kW | Rated Operational Voltage | Main Circuit 690 V AC |
Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 18 kiloampere rms | Standards | IEC 60947-3 |
Switches Operating Mechanism | 22 (Between the Poles) | Terminal Type | Lug terminals |
Terminal Width | 39 mm | Tightening Torque | 50 ... 75 N·m |
Tightening Torque | 50 ... 75 N·m | Object Classification Code | Q |
ETIM 8 | EC001040 - Fuse switch disconnector | ETIM 9 | EC001040 - Fuse switch disconnector |
UNSPSC | 39122233 | IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
eClass | V11.1 : 27371401 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SCA022837R8000 |
Specifications may be subject to change without notice