Product Model
OS63GDS40N2K

Selling Points
- 1Engineered for the most demanding applications with knife contact design ensuring reliable electrical life.
- 2Easy and cost-efficient installation, maintenance, and use with adjustable shaft and snap-on auxiliary contacts.
- 3Interlocking fuse covers prevent opening while the switch is in “ON” position, reducing the risk of electric shock.
- 4Adjustable shaft for external handles, mounting feet, and snap-on auxiliary contacts significantly reduce installation time and costs.
- 5Rated for up to 63A with a maximum fuse power dissipation of 7.5W in open air and 5% derating in totally enclosed environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Pollution Degree | 3 | Product Net Width | 191 mm |
Product Net Height | 125 mm | Product Net Depth / Length | 121 mm |
Product Net Weight | 1.51 kg 3.33 lb | Cable Cross-Section | 2.5 ... 25 mm² |
Connecting Capacity | Stranded 2.5 ⦠25 mm² Flexible 2.5 ⦠25 mm² | Conventional Free-air Thermal Current (Ith) | Π= 40 °C 63 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 63 A | Fourth Pole Position | Right Side |
Fourth Pole Type | Switched - With Solid Link | Fuse Size | NH000 |
Fuse System | DIN | Handle Type | Direct mounted handle included |
Mounting Type | Base mounting | Number of Poles | 4P |
Operating Mode | Side Operated | Pollution Degree | 3 |
Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out | Power Loss | at Rated Operating Conditions per Pole 4 W |
Rated Conditional Short-Circuit Current (Inc) | (690 V) 80 kA | Rated Current (In) | Main Circuit 63 A |
Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | 1000 V |
Rated Operational Current AC-21A (Ie) | (500 V) 63 A (690 V) 63 A | Rated Operational Current AC-22A (Ie) | (500 V) 63 A (690 V) 63 A |
Rated Operational Current AC-23A (Ie) | (500 V) 63 A (690 V) 63 A | Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 18.5 kW (400 V) 30 kW (415 V) 30 kW (500 V) 37 kW (690 V) 55 kW |
Rated Operational Voltage | Main Circuit 690 V AC | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 2.5 kiloampere rms |
Standards | IEC 60947-3 | Switches Operating Mechanism | 40 (Right Side) |
Terminal Type | Screw Terminals | Tightening Torque | 3 N·m 4 N·m |
Wire Stripping Length | Main Circuit 12 mm Main Circuit 0.47 in | Wire Stripping Length | Main Circuit 12 mm Main Circuit 0.47 in |
Tightening Torque | 3 N·m 4 N·m | Object Classification Code | Q |
ETIM 8 | EC001040 - Fuse switch disconnector | ETIM 9 | EC001040 - Fuse switch disconnector |
UNSPSC | 39122233 | IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
eClass | V11.1 : 27371401 | WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
Manufacturer ID | 1SCA116403R1001 |
Specifications may be subject to change without notice