Product Model

OS63GDS40N2K

In Stock
Last updated: 2025/4/22
ABB OS63GDS40N2K

Selling Points

  • 1Engineered for the most demanding applications with knife contact design ensuring reliable electrical life.
  • 2Easy and cost-efficient installation, maintenance, and use with adjustable shaft and snap-on auxiliary contacts.
  • 3Interlocking fuse covers prevent opening while the switch is in “ON” position, reducing the risk of electric shock.
  • 4Adjustable shaft for external handles, mounting feet, and snap-on auxiliary contacts significantly reduce installation time and costs.
  • 5Rated for up to 63A with a maximum fuse power dissipation of 7.5W in open air and 5% derating in totally enclosed environments.
Product Details
OS63GDS40N2K
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Pollution Degree
3
Product Net Width
191 mm
Product Net Height
125 mm
Product Net Depth / Length
121 mm
Product Net Weight
1.51 kg 3.33 lb
Cable Cross-Section
2.5 ... 25 mm²
Connecting Capacity
Stranded 2.5 … 25 mm² Flexible 2.5 … 25 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 63 A
Conventional Thermal Current (Ithe)
Fully Enclosed 63 A
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - With Solid Link
Fuse Size
NH000
Fuse System
DIN
Handle Type
Direct mounted handle included
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Side Operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4 W
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Current (In)
Main Circuit 63 A
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(500 V) 63 A (690 V) 63 A
Rated Operational Current AC-22A (Ie)
(500 V) 63 A (690 V) 63 A
Rated Operational Current AC-23A (Ie)
(500 V) 63 A (690 V) 63 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 18.5 kW (400 V) 30 kW (415 V) 30 kW (500 V) 37 kW (690 V) 55 kW
Rated Operational Voltage
Main Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kiloampere rms
Standards
IEC 60947-3
Switches Operating Mechanism
40 (Right Side)
Terminal Type
Screw Terminals
Tightening Torque
3 N·m 4 N·m
Wire Stripping Length
Main Circuit 12 mm Main Circuit 0.47 in
Wire Stripping Length
Main Circuit 12 mm Main Circuit 0.47 in
Tightening Torque
3 N·m 4 N·m
Object Classification Code
Q
ETIM 8
EC001040 - Fuse switch disconnector
ETIM 9
EC001040 - Fuse switch disconnector
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5291 >> Fuse switch disconnector
eClass
V11.1 : 27371401
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA116403R1001

Specifications may be subject to change without notice