Selling Points

  • 1High Amperage Rating: Supports 630 to 800 A, ensuring reliable performance in demanding electrical systems.
  • 2Durable Construction: Made from high-quality plastic, providing long-lasting protection and resistance to environmental factors.
  • 3Easy Installation: Features a snap-on mount design for quick and secure installation, reducing downtime and increasing efficiency.
  • 4Compatibility: Specifically designed for use with OT/OTM630 to 800 3-Pole Non-Fusible Disconnect Switches, ensuring seamless integration.
  • 5Gray Color: Available in a gray color, enhancing visibility and ease of identification in industrial settings.
Product Details
OS800B13N1P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Pollution Degree
3
Product Net Width
429 mm
Product Net Height
306 mm
Product Net Depth / Length
233 mm
Product Net Weight
18.964 kg 41.81 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 800 A
Conventional Thermal Current (Ithe)
Fully Enclosed 720 A
Fourth Pole Position
Left Side
Fourth Pole Type
Switched - With Solid Link
Fuse Size
C1-C3
Fuse System
British Standard
Handle Type
Pistol handle and shaft included
Mounting Type
Base mounting
Number of Poles
4
Operating Mode
Front Operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 75 W
Rated Conditional Short-Circuit Current (Inc)
(690 V) 80 kA
Rated Current (In)
Main Circuit 800 A
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(500 V) 800 A (690 V) 800 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 800 A (500 V) 800 A (690 V) 800 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 250 kW (400 V) 450 kW (415 V) 450 kW (500 V) 560 kW (690 V) 710 kW
Rated Operational Voltage
Main Circuit 690 V AC
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 18 kiloampere rms
Standards
IEC 60947-3
Switches Operating Mechanism
13 (Between the Poles)
Terminal Type
Lug terminals
Terminal Width
39 mm
Tightening Torque
50 ... 75 N·m
Tightening Torque
50 ... 75 N·m
Object Classification Code
Q
ETIM 8
EC001040 - Fuse switch disconnector
ETIM 9
EC001040 - Fuse switch disconnector
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5291 >> Fuse switch disconnector
eClass
V11.1 : 27371401
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022837R5410

Specifications may be subject to change without notice