Product Model

OT1000BBRR3TZ

In Stock
Last updated: 2025/4/21
ABB OT1000BBRR3TZ

Selling Points

  • 1High-Performance Protection: The OT1000BBRR3TZ provides reliable and safe operation with a robust steel enclosure.
  • 2IP65 Rating: Ensures protection against dust and water, making it suitable for harsh industrial environments.
  • 33-Pole Design: Suitable for 3-phase systems, offering efficient and reliable switching.
  • 4Steel Enclosure: Durable and resistant to corrosion, ensuring long-lasting performance.
  • 5Customizable: Available with 2 NO and 1 NC auxiliary contacts, allowing for flexible configuration to meet specific needs.
Product Details
OT1000BBRR3TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
1200 mm
Product Net Depth / Length
330 mm
Product Net Weight
62 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
4xring-flange / 4xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 8pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 1000 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Position of PE Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 19 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Recommended Screw Driver
Main Circuit M12
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 75 N·m
Recommended Screw Driver
Main Circuit M12
Tightening Torque
Main Circuit 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642715
E-Number (Norway)
1429137
E-Number (Sweden)
3140636
Manufacturer ID
1SCA022340R3100

Specifications may be subject to change without notice