Product Model

OT1000BFCC3T

In Stock
Last updated: 2025/4/25
ABB OT1000BFCC3T

Selling Points

  • 1Built with rigid glass reinforced polycarbonate for durability and resistance to UV radiation.
  • 2Protected against low-pressure water jets, making it suitable for both indoor and outdoor applications.
  • 3Equipped with a padlockable handle that can secure up to three padlocks for enhanced safety.
  • 4Features an interlocked cover that can be defeated for easy access, ensuring safety during maintenance.
  • 5Comes with PE terminals for secure electrical connections.
Product Details
OT1000BFCC3T
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
560 mm
Product Net Height
760 mm
Product Net Depth / Length
250 mm
Product Net Weight
33.73 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
2xII-flange / 2xII-flange
Connecting Capacity Main Circuit
Hole Diameter 12 mm Screw Clamp / PE Terminal 4pc,25 ... 120 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 1000 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Handle Color
Black
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Position of PE Terminals
Top In - Bottom Out
Power Loss
at Rated Operating Conditions per Pole 19 W
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Recommended Screw Driver
Main Circuit M12
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 75 N·m
Recommended Screw Driver
Main Circuit M12
Tightening Torque
Main Circuit 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3642431
E-Number (Norway)
1428983
E-Number (Sweden)
3140238
Manufacturer ID
1SCA022277R1620

Specifications may be subject to change without notice