Product Model
OT1000BUUR3TZ

Selling Points
- 1High-power rating: 1000A/560kW for demanding electrical applications.
- 2Robust construction: Steel sheet enclosure with IP65 protection against dust and water.
- 3Versatile mounting: Suitable for mounting auxiliary contacts, ideal for various electrical configurations.
- 4Enhanced safety: Meets EN 60947-3 and IEC 61000-6-3/4 standards for reliable performance.
- 5Durable design: Lakkert varmgalvanisert stålplate (hot-dip galvanized steel plate) for long-lasting durability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
Product Net Width | 800 mm | Product Net Height | 1200 mm |
Product Net Depth / Length | 330 mm | Product Net Weight | 69.87 kg |
Cable Entry Position | Bottom/Bottom | Cable Outlets Per Side | Blank / 8xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm |
Connecting Capacity Main Circuit | Hole Diameter 12 mm Screw Clamp / PE Terminal 10pc,25 ... 120 mm² | Conventional Thermal Current (Ithe) | Fully Enclosed 1000 A |
Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
Handle Color | Black | Handle Type | Pistol handle |
Impact Resistance Rating | Housing IK09 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
Mounted Auxiliary Contacts | 2 NO, 1 NC | Neutral Type | No neutral terminal |
Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 2 |
Number of Poles | 3P | Pollution Degree | 3 |
Power Loss | at Rated Operating Conditions per Pole 19 W | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 1000 A (500 V) 1000 A (690 V) 1000 A |
Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 560 kW (500 V) 710 kW (690 V) 1000 kW | Rated Operational Voltage | Main Circuit 1000 V |
Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 110 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
Recommended Screw Driver | Main Circuit M12 | Special Functions | EMC |
Standards | IEC 60947-1, -3 | Tightening Torque | Main Circuit 75 N·m |
Recommended Screw Driver | Main Circuit M12 | Tightening Torque | Main Circuit 75 N·m |
Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
WEEE Category | 4. Large Equipment (Any External Dimension More Than 50 cm) | E-Number (Finland) | 3601784 |
E-Number (Norway) | 1429465 | E-Number (Sweden) | 3141238 |
Manufacturer ID | 1SCA022513R8850 |