Product Model

OT100FT4N2

In Stock
Last updated: 2025/4/26
ABB OT100FT4N2

Selling Points

  • 1High Amperage Rating: 100A for reliable power handling.
  • 2Front Operated Design: Easy to use with a front-operated mechanism.
  • 3IP20 Enclosure: Provides protection against solid objects and dust.
  • 4Versatile Voltage Rating: Suitable for 750 VAC applications.
  • 5Durable Construction: Built to withstand harsh industrial environments.
Product Details
OT100FT4N2
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301264D0201
Pollution Degree
3
Product Net Width
100 mm
Product Net Height
96.5 mm
Product Net Depth / Length
66.5 mm
Product Net Weight
0.5 kg
Cable Cross-Section
Cu 10 ... 70 mm²
Connecting Capacity Main Circuit
Flexible 1x Cu 10…70 mm² Stranded 1x Cu 10…70 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 115 A
Conventional Thermal Current (Ithe)
Fully Enclosed 115 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Door mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 4.0 W
Rated Conditional Short-Circuit Current (Inc)
(125 A fuse, 415 V) 50 kA (125 A fuse, 690 V) 10 kA (63 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 100 A (500 V) 100 A (690 V) 100 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 100 A (500 V) 100 A (690 V) 100 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 80 A (500 V) 60 A (690 V) 40 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 22 kW (400 ... 415 V) 37 kW (500 V) 37 kW (690 V) 37 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 3.6 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 2.5 kA
Recommended Screw Driver
Main Circuit Hexagon 4
Special Functions
No
Standards
IEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Wire Stripping Length
Main Circuit 18-21 mm
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
100 A
Horsepower Rating UL/CSA
(110 ... 120 V AC) Single Phase 5 Hp (240 V AC) Single Phase 15 Hp (440 ... 480 V AC) Single Phase 25 Hp (550 ... 600 V AC) Single Phase 20 Hp (220 ... 240 V AC) Three Phase 30 Hp (440 ... 480 V AC) Three Phase 50 Hp (550 ... 600 V AC) Three Phase 50 Hp
Wire Stripping Length
Main Circuit 18-21 mm
Recommended Screw Driver
Main Circuit Hexagon 4
Tightening Torque
acc. IEC 60947-1 6 N·m
Tightening Torque UL/CSA
55 in·lb
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3601408
E-Number (Norway)
4363545
E-Number (Sweden)
3171087
Manufacturer ID
1SCA105031R1001

Specifications may be subject to change without notice