OT100G2-3DS
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301333D0201
Pollution Degree
3
Product Net Width
64 mm
Product Net Height
81 mm
Product Net Depth / Length
70 mm
Product Net Weight
0.267 kg
Connecting Capacity Main Circuit
Flexible with Ferrule 1/2x Cu 1.5…4 mm² Solid 1/2x Cu 1.5…6 mm² Flexible 1x Cu 1.5…35 mm² Flexible 2x Cu 1.5…16 mm² Stranded 1x Cu 1.5…35 mm² Stranded 2x Cu 1.5…16 mm²
Conventional Free-air Thermal Current (Ith)
100 A
Conventional Thermal Current (Ithe)
100 A
Degree of Protection
Front IP20
Handle Type
Handle not included
Maximum Mounted Auxiliary Contacts
4 NO, 4 NC
Mechanical Durability
Nr. Operations 100000
Mounting Type
Door mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 5.3 W
Rated Conditional Short-Circuit Current (Inc)
(100 A fuse, ≤415 V) 5 kA (80 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
acc. to IEC 60947-1 800 V
Rated Operational Current AC-21A (Ie)
(415 V) 100 A (690 V) 80 A
Rated Operational Current AC-22A (Ie)
(415 V) 100 A (690 V) 80 A
Rated Operational Current AC-23A (Ie)
(415 V) 80 A (690 V) 40 A
Rated Operational Power AC-23A (Pe)
(415 V) 45 kW (690 V) 37 kW
Rated Operational Voltage
Main Circuit 800 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 3.5 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 1.5 kA for 0.2 s 2.5 kA
Recommended Screw Driver
Main Circuit Pozidriv 2
Special Functions
No
Standards
IEC60947-3 UL60947-4-1 CSA C22.2 No.14
Switches Operating Mechanism
Mechanism on Top of the Switch
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 2 N·m
Wire Stripping Length
Main Circuit 13-16 mm Main Circuit 0.51-0.63 in
Maximum Operating Voltage UL/CSA
600 V
Wire Size
1x 16-2 AWG 2x 16-8 AWG
Wire Stripping Length
Main Circuit 13-16 mm Main Circuit 0.51-0.63 in
Recommended Screw Driver
Main Circuit Pozidriv 2
Tightening Torque
acc. IEC 60947-1 2 N·m
Tightening Torque UL/CSA
UL 18 lbf·in
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA162565R1001

Specifications may be subject to change without notice