Product Model

OT1250E03W8P

In Stock
Last updated: 2025/4/20
ABB OT1250E03W8P

Selling Points

  • 1High thermal current up to 1250 A in both free-air and fully enclosed conditions.
  • 2Robust 3-pole, front-operated switch-disconnector with a black IP65 handle and shaft.
  • 3Wide phase distance of 185 mm for enhanced safety and reliability.
  • 4Integrated terminal bolt kit for easy installation and maintenance.
  • 5Compliance with IEC 60947-3 standards and CE certification for safety assurance.
Product Details
OT1250E03W8P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301233D0201
Pollution Degree
3
Product Net Width
544.5 mm
Product Net Height
306 mm
Product Net Depth / Length
145.5 mm
Product Net Weight
19.5 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1250 A
Degree of Protection
Front IP00
Distance Between Phases
Phase distance 185 mm
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
6000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 29 W
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
Wide phase distance 185
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 03 (Left Side)
Terminal Type
Lug terminals
Terminal Width
50 mm
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
E-Number (Finland)
3661694
Manufacturer ID
1SCA022871R8540

Specifications may be subject to change without notice