Product Model

OT1250EM03P

In Stock
Last updated: 2025/4/19
ABB OT1250EM03P

Selling Points

  • 1Built with high-performance materials for reliable operation.
  • 2Enhances performance with fast and efficient switching.
  • 3Suitable for confined spaces with a small footprint area.
  • 4Offers a wide variety of accessories for flexible installation.
  • 5Provides secure operation with a padlockable handle in off-position.
Product Details
OT1250EM03P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301233D0201
Pollution Degree
3
Product Net Width
349.5 mm
Product Net Height
306 mm
Product Net Depth / Length
234 mm
Product Net Weight
16.2 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1250 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
6000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 29 W
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
03 (Left Side) Mechanism turned 90 degrees
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Utilization
Earthing Switch Use
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5290 >> Disconnect switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3600195
Manufacturer ID
1SCA115708R1001

Specifications may be subject to change without notice