Product Model
OT125ETUU3TZ

Selling Points
- 1125A for reliable power handling.
- 2Fully enclosed with a 3.6 kA short circuit making capacity.
- 3Base mount and DIN rail mount options for flexible installation.
- 4Ensures fast and secure switching operations.
- 5Meets UL508 and IEC 60947-3 standards for safety and reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
Product Net Width | 250 mm | Product Net Height | 400 mm |
Product Net Depth / Length | 180 mm | Product Net Weight | 10 kg |
Cable Cross-Section | 120 mm² | Cable Entry Position | Up/Down |
Cable Outlets Per Side | Blank / Blank, Knock-outs: 10mm, 12.5mm, 20.5mm, 25.5mm | Conventional Thermal Current (Ithe) | Fully Enclosed 160 A |
Degree of Protection | acc. to IEC 60529 IP65 | Enclosure Material | Steel sheet |
Handle Color | Black | Handle Type | Pistol handle |
Maximum Mounted Auxiliary Contacts | 2 NO, 1 NC | Mounted Auxiliary Contacts | 1 NO, 1 NC |
Number of Poles | 3P | Pollution Degree | 3 |
Power Loss | at Rated Operating Conditions per Pole 4 W | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 750 V |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 90 A (690 V) 70 A |
Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 55 kW (690 V) 55 kW | Rated Operational Voltage | Main Circuit 750 V |
Special Functions | EMC | Object Classification Code | Q |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | E-Number (Finland) | 3601750 |
Manufacturer ID | 1SCA022752R6850 |
Specifications may be subject to change without notice