Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Degree of Protection | acc. to IEC 60529 IP65 | Pollution Degree | 3 |
Product Net Width | 280 mm | Product Net Height | 380 mm |
Product Net Depth / Length | 130 mm | Product Net Weight | 3.4 kg |
Cable Cross-Section | 10 ... 70 mm² | Cable Entry Position | Top/Bottom |
Cable Outlets Per Side | II-flange / II-flange | Connecting Capacity Main Circuit | Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 2pc,10 ... 70 mm² |
Conventional Thermal Current (Ithe) | Fully Enclosed 125 A | Degree of Protection | acc. to IEC 60529 IP65 |
Enclosure Material | Plastic | Enclosure Type | Fibox |
Handle Color | Black | Handle Type | Pistol handle |
Impact Resistance Rating | Housing IK08 | Maximum Mounted Auxiliary Contacts | 2 NO, 2 NC |
Mounted Auxiliary Contacts | 1 NO, 1 NC | Neutral Type | No neutral terminal |
Number of Auxiliary Contacts NC | 1 | Number of Auxiliary Contacts NO | 1 |
Number of Poles | 3P | Pollution Degree | 3 |
Position of Line Terminals | Top In - Bottom Out | Rated Conditional Short-Circuit Current (Inc) | 24 kA |
Rated Impulse Withstand Voltage (Uimp) | 12 kV | Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A | Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A |
Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW | Rated Operational Voltage | Main Circuit 1000 V |
Rated Short-Circuit Making Capacity (Icm) | (690 V AC) 12 kA | Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 4 kA |
Recommended Screw Driver | Main Circuit Hexagon 4 | Standards | IEC 60947-1, -3 |
Terminal Type | Screw Terminals | Tightening Torque | Main Circuit 6 N·m |
Wire Stripping Length | 20 mm | Wire Stripping Length | 20 mm |
Recommended Screw Driver | Main Circuit Hexagon 4 | Tightening Torque | Main Circuit 6 N·m |
Object Classification Code | Q | ETIM 8 | EC000216 - Switch disconnector |
ETIM 9 | EC000216 - Switch disconnector (low voltage) | UNSPSC | 39122205 |
IDEA Granular Category Code (IGCC) | 5166 >> Safety switch | eClass | V11.1 : 27371403 |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) | E-Number (Finland) | 3640405 |
E-Number (Norway) | 1428975 | E-Number (Sweden) | 3134565 |
Manufacturer ID | 1SCA148608R1001 |
Specifications may be subject to change without notice