Product Model

OT125GFCC4A

In Stock
Last updated: 2025/4/22
ABB OT125GFCC4A

Selling Points

  • 1125A for robust power handling.
  • 2Suitable for multiple circuit connections.
  • 3Durable against dust and water.
  • 4Easy-to-use control element.
  • 5Enhanced safety with defeatable interlocking.
Product Details
OT125GFCC4A
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
280 mm
Product Net Height
380 mm
Product Net Depth / Length
130 mm
Product Net Weight
3.6 kg
Cable Cross-Section
10 ... 70 mm²
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
II-flange / II-flange
Connecting Capacity Main Circuit
Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 2pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Plastic
Enclosure Type
Fibox
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK08
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
1 NO, 1 NC
Neutral Type
Switchable neutral
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
1
Number of Poles
4P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Rated Conditional Short-Circuit Current (Inc)
24 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 12 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 4 kA
Recommended Screw Driver
Main Circuit Hexagon 4
Standards
IEC 60947-1, -3
Terminal Type
Screw Terminals
Tightening Torque
Main Circuit 6 N·m
Wire Stripping Length
20 mm
Wire Stripping Length
20 mm
Recommended Screw Driver
Main Circuit Hexagon 4
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA148611R1001

Specifications may be subject to change without notice