Product Model

OT125GUUR3AZ

In Stock
Last updated: 2025/4/23
ABB OT125GUUR3AZ

Selling Points

  • 1High Performance: Designed for 3-pole applications with a rated operational current of 125A and a power rating of 55kW.
  • 2Enhanced Safety: Features IP65 protection and a robust steel sheet enclosure for reliable operation.
  • 3Versatile Use: Suitable for various applications, including repair and maintenance, with a red-yellow pistol handle for easy identification.
  • 4Comprehensive Features: Includes mounted auxiliary contact (1NO1NC) and interlocked cover for added security.
  • 5Durable Construction: Constructed with high-quality materials, ensuring long-lasting performance in demanding environments.
Product Details
OT125GUUR3AZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
400 mm
Product Net Height
400 mm
Product Net Depth / Length
230 mm
Product Net Weight
14.8 kg
Cable Cross-Section
10 ... 70 mm²
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
Blank / 4xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Screw Clamp 10 ... 70 mm² Screw Clamp / PE Terminal 2pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 125 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Enclosure Type
MSC
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 2 NC
Mounted Auxiliary Contacts
1 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
1
Number of Poles
3P
Pollution Degree
3
Position of Line Terminals
Bottom In - Bottom Out
Rated Conditional Short-Circuit Current (Inc)
24 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 125 A (500 V) 125 A (690 V) 125 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 55 kW (500 V) 75 kW (690 V) 110 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V AC) 12 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 4 kA
Recommended Screw Driver
Main Circuit Hexagon 4
Special Functions
EMC
Standards
IEC 60947-1, -3
Terminal Type
Screw Terminals
Tightening Torque
Main Circuit 6 N·m
Wire Stripping Length
20 mm
Wire Stripping Length
20 mm
Recommended Screw Driver
Main Circuit Hexagon 4
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA148443R1001