Product Model

OT1600E03W4P

In Stock
Last updated: 2025/4/22
ABB OT1600E03W4P

Selling Points

  • 1IP65 Protected Handle: The handle is IP65 protected, ensuring durability in harsh environments.
  • 2Padlockable and Adjustable: The handle is padlockable in the off-position and features an adjustable shaft for various installation depths.
  • 3Wide Phase Distance: Offers a wide phase distance of 140 mm, enhancing safety and reliability.
  • 4High Current Rating: Supports up to 1600 A operational current, making it suitable for demanding applications.
  • 5Compliant with IEC Standards: Meets IEC standards for insulation voltage (1000 V) and impulse withstand voltage (12 kV).
Product Details
OT1600E03W4P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301233D0201
Pollution Degree
3
Product Net Width
454.5 mm
Product Net Height
372 mm
Product Net Depth / Length
167 mm
Product Net Weight
16.5 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 1600 A
Conventional Thermal Current (Ithe)
Fully Enclosed 1600 A
Degree of Protection
Front IP00
Distance Between Phases
Phase distance 140 mm
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
6000
Mounting Type
Base mounting
Number of Poles
3P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 48 W
Rated Conditional Short-Circuit Current (Inc)
(1250 A fuse, 415 V) 80 kA (1250 A fuse, 500 V) 100 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 1600 A (500 V) 1600 A (690 V) 1600 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 1250 A (500 V) 1250 A (690 V) 1250 A
Rated Operational Power AC-23A (Pe)
(400 ... 415 V) 710 kW (500 V) 900 kW (690 V) 1200 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 110 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 50 kA
Special Functions
Wide phase distance 140
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 03 (Left Side)
Terminal Type
Lug terminals
Terminal Width
50 mm
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Tightening Torque
acc. IEC 60947-1 50 … 75 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Finland)
3661762
Manufacturer ID
1SCA022865R9860

Specifications may be subject to change without notice