Product Model

OT160E13WCLP

In Stock
Last updated: 2025/4/27
ABB OT160E13WCLP

Selling Points

  • 1Compact and powerful design for universal applications.
  • 2Reduced stock expenses with modular construction.
  • 3Easy to use and install with integrated terminal clamps.
  • 4High-rated insulation voltage and dielectric strength for safety.
  • 5Measurable savings across its entire lifecycle from installation to replacement.
Product Details
OT160E13WCLP
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC303050D0201
Pollution Degree
3
Product Net Width
237 mm 9.33 in
Product Net Height
150 mm 5.91 in
Product Net Depth / Length
160 mm 6.3 in
Product Net Weight
3.8 kg 8.38 lb
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP20
Distance Between Phases
Wide phase distance
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out, Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 2.4 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-31B (Ie)
(380 ... 415 V) 160 A
Rated Operational Current AC-33B (Ie)
(380 ... 415 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 90 kW (500 V) 110 kW (690 V) 160 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kiloampere rms
Switches Operating Mechanism
Mechanism Between the Poles 13 (Between the Poles)
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Transition Type
Closed
Ampere Rating
160 A
Tightening Torque
acc. IEC 60947-1 15 ... 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA108506R1001

Specifications may be subject to change without notice