Product Model

OT160EVLRR6AZ

In Stock
Last updated: 2025/4/25
ABB OT160EVLRR6AZ

Selling Points

  • 1High operational power rating: 710 kW at 400-415 V, 900 kW at 500 V, 1200 kW at 690 V.
  • 2Exceptional thermal current: 1600 A at 40°C in free air and fully enclosed.
  • 3Reliable insulation: Rated insulation voltage up to 1000 V according to IEC/EN 60664-1.
  • 4Durable construction: Front IP00 degree of protection, mechanical durability of 6000 cycles.
  • 5Versatile mounting options: Base mounting with standard dimensions (414.5 mm x 372 mm x 167 mm).
Product Details
OT160EVLRR6AZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
600 mm
Product Net Depth / Length
230 mm
Product Net Weight
33.6 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
8xring-flange / 8xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Enclosure Type
MSC
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
2 NO, 1 NC
Mounted Auxiliary Contacts
2 NO, 1 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
1
Number of Auxiliary Contacts NO
2
Number of Poles
6P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 88 kW (500 V) 112 kW (690 V) 144 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Standards
IEC 60947-1, -3
Terminal Type
Bolt
Tightening Torque
Main Circuit 6 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA148020R1001

Specifications may be subject to change without notice