Product Model

OT160EVSUR6TZ

In Stock
Last updated: 2025/4/22
ABB OT160EVSUR6TZ

Selling Points

  • 1High IP65 protection against dust and water.
  • 2Self-extinguishing plastic for enhanced safety.
  • 3Compliance with IEC 60947-3 and EN60204 standards.
  • 4Suitable for 4- and 5-wire systems.
  • 5Front-operated design with padlockable handle for secure operation.
Product Details
OT160EVSUR6TZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
800 mm
Product Net Depth / Length
230 mm
Product Net Weight
38.5 kg
Cable Entry Position
Bottom/Bottom
Cable Outlets Per Side
Blank / 8xring-flange+ø25.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Stainless steel
Handle Color
Stainless Steel
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Power Loss
at Rated Operating Conditions per Pole 3.2 W
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 750 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 80 kW (500 V) 112 kW (690 V) 144 kW
Rated Operational Voltage
Main Circuit 750 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Special Functions
EMC
Standards
IEC 60947-1, -3
Tightening Torque
Main Circuit 6 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA125650R1001

Specifications may be subject to change without notice