Product Model

OT160EVTRR6AZ

In Stock
Last updated: 2025/4/23
ABB OT160EVTRR6AZ

Selling Points

  • 1IP65 Protection: Ensures reliable operation in harsh environments.
  • 2Robust Design: Built to withstand heavy use and harsh conditions.
  • 3High Current Ratings: Handles up to 200 A with a fully enclosed thermal current of 160 A.
  • 4Easy Mounting: Designed for door or side wall mounting with included handle OHB65J6 and shaft OXP6x1.
  • 5Comprehensive Certifications: Meets IEC standards and includes CE, DNV, and KEMA certificates.
Product Details
OT160EVTRR6AZ
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
acc. to IEC 60529 IP65
Pollution Degree
3
Product Net Width
800 mm
Product Net Height
600 mm
Product Net Depth / Length
230 mm
Product Net Weight
33.6 kg
Cable Entry Position
Top/Bottom
Cable Outlets Per Side
8xring-flange / 8xring-flange, Knock-outs: 3x10mm, 12.5mm, 20.5mm, 25.5mm, 32.5mm
Connecting Capacity Main Circuit
Hole Diameter 8 mm Screw Clamp / PE Terminal 4pc,10 ... 70 mm²
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
acc. to IEC 60529 IP65
Enclosure Material
Steel sheet
Enclosure Type
MSC
Handle Color
Red / Yellow
Handle Type
Pistol handle
Impact Resistance Rating
Housing IK09
Maximum Mounted Auxiliary Contacts
4 NO, 2 NC
Mounted Auxiliary Contacts
4 NO, 2 NC
Neutral Type
No neutral terminal
Number of Auxiliary Contacts NC
2
Number of Auxiliary Contacts NO
4
Number of Poles
6P
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out
Rated Conditional Short-Circuit Current (Inc)
40.5 kA
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(380 ... 415 V) 88 kW (500 V) 112 kW (690 V) 144 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(1000 V AC) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Recommended Screw Driver
Main Circuit M8
Special Functions
EMC
Standards
IEC 60947-1, -3
Terminal Type
Bolt
Tightening Torque
Main Circuit 6 N·m
Recommended Screw Driver
Main Circuit M8
Tightening Torque
Main Circuit 6 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122205
IDEA Granular Category Code (IGCC)
5166 >> Safety switch
eClass
V11.1 : 27371403
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
Manufacturer ID
1SCA148028R1001

Specifications may be subject to change without notice