Product Model

OT160G04

In Stock
Last updated: 2025/4/27
ABB OT160G04

Selling Points

  • 1High current rating of 160A for efficient power management.
  • 2Compact design with dimensions of 130 mm H x 150 mm W x 73 mm D.
  • 3Meets IP20 protection standards for safe operation.
  • 4Suitable for both DIN rail and panel mounting options.
  • 5Compliant with UL98, CSA C22.2 NO.4, and IEC 60947-3 standards.
Product Details
OT160G04
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP20
Environmental Information
1SCC301267D0201
Pollution Degree
3
Product Net Width
150 mm
Product Net Height
130 mm
Product Net Depth / Length
73 mm
Product Net Weight
1 kg
Cable Cross-Section
Cu 10 ... 70 mm²
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 160 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP20
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Type
Handle and shaft not included
Lock Type
No
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front and side operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Conditional Short-Circuit Current (Inc)
(200 A fuse, 500 V) 100 kA (200 A fuse, 690 V) 50 kA
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 160 A (500 V) 160 A (690 V) 160 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 45 kW (400 ... 415 V) 75 kW (500 V) 90 kW (690 V) 132 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 12 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 4 kA
Special Functions
No
Standards
IEC 60947-3 / UL 98 / CSA C22.2 NO.4
Switches Operating Mechanism
Mechanism at the End of the Switch 04 (Left Side)
Terminal Type
Screw Terminals
Tightening Torque
acc. IEC 60947-1 6 N·m
Maximum Operating Voltage UL/CSA
600 V
Ampere Rating
125 A
Horsepower Rating UL/CSA
(240 V AC) Single Phase 20 Hp (440 ... 480 V AC) Single Phase 30 Hp
Tightening Torque
acc. IEC 60947-1 6 N·m
Tightening Torque UL/CSA
53 in·lb
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
UNSPSC
39122233
IDEA Granular Category Code (IGCC)
5293 >> Switch disconnector
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
E-Number (Norway)
4372123
Manufacturer ID
1SCA135135R1001

Specifications may be subject to change without notice