Product Model

OT250E02P

In Stock
Last updated: 2025/4/18
ABB OT250E02P

Selling Points

  • 1Designed to withstand 12 kilovolt impulse voltage and 1000 volt operational voltage.
  • 2Rated for 8 kiloampere short-time withstand current and 55 kiloampere low voltage short-time withstand current.
  • 3Front-operated mechanism with base mounting for flexible installation orientation.
  • 4IP65-rated handle and shaft for protection against environmental factors.
  • 5Meets IEC 60947-3 standards for switch-disconnectors, ensuring high-quality performance.
Product Details
OT250E02P
ABB

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Degree of Protection
Front IP00
Environmental Information
1SCC301265D0201
Pollution Degree
3
Product Net Width
110.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Conventional Free-air Thermal Current (Ith)
Θ = 40 °C 250 A
Conventional Thermal Current (Ithe)
Fully Enclosed 250 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
2
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 6.5 W
Rated Impulse Withstand Voltage (Uimp)
12 kV
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 1000 V
Rated Operational Current AC-21A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A (1000 V) 250 A
Rated Operational Current AC-22A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Current AC-23A (Ie)
(380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A
Rated Operational Power AC-23A (Pe)
(220 ... 240 V) 75 kW (400 ... 415 V) 145 kW (500 V) 170 kW (690 V) 250 kW
Rated Operational Voltage
Main Circuit 1000 V
Rated Short-Circuit Making Capacity (Icm)
(690 V) 30 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 8 kA
Special Functions
No
Standards
IEC 60947-3
Switches Operating Mechanism
Mechanism at the End of the Switch 02 (Left Side)
Terminal Type
Lug terminals
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Tightening Torque
acc. IEC 60947-1 15 … 22 N·m
Object Classification Code
Q
ETIM 8
EC000216 - Switch disconnector
ETIM 9
EC000216 - Switch disconnector (low voltage)
eClass
V11.1 : 27371403
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SCA022735R2500

Specifications may be subject to change without notice